# IEC103M.CFG # # Example file for use with the IEC-870-5-103 Master protocol driver on the # MVI69 platform (two master ports). # # # This section contains the backplane configuration information. It is used # to determine the number of registers moved between the module and the # processor. [Backplane Configuration] Module Name : MVI69-103M DEMO MODULE Read Register Start : 0 #Starting DB address of data read by processor Read Register Count : 480 #Number of regs read by processor Write Register Start : 480 #Starting DB address of data received from processor Write Register Count : 480 #Number of regs to be received from processor Failure Flag Count : 0 #Determines if BP failure will cause protocol to be #disabled (0=Ignore, >0 = failure count to disable) Pass-Through Events : Y #Pass event messages to processor Block Transfer Size : 60 #60, 120, 240 word transfer area for MVI69 module # This is the configuration for the IEC-870-5-103 master port emulated on the # module. [IEC-870-5-103 Master] Session Count : 1 #1 to 16 - maximum number of slaves on all channels [IEC-870-5-103 Master Port 0] # Communication Parameters Baud Rate : 9600 #Baud rate for port 110-115200 Parity : E #N=None, O=Odd, E=Even, M=Mark, S=Space RTS On : 0 #0-65536 mSec before message RTS Off : 1 #0-65536 mSec after message3 Minimum Delay : 10 #Minimum # of mSec before response sent Receive Timeout : 2000 #Maximum mSec from first char to last to wait # These parameters are protocol specific Single char ACK F0,1 or 3 : Y #Single E5 resp to ACK func 0, 1 & 3 req (Y/N) [IEC-870-5-103 Master Port 1] # Communication Parameters Baud Rate : 9600 #Baud rate for port 110-115200 Parity : E #N=None, O=Odd, E=Even, M=Mark, S=Space RTS On : 0 #0-65536 mSec before message RTS Off : 1 #0-65536 mSec after message Minimum Delay : 10 #Minimum # of mSec before response sent Receive Timeout : 2000 #Maximum mSec from first char to last to wait # These parameters are protocol specific Single char ACK F0,1 or 3 : Y #Single E5 resp to ACK func 0, 1 & 3 req (Y/N) # This section is used to define session 0 which runs on Port 0 [IEC-103 Master Session 0] Communication Port : 0 #Index of COM port for session (0) Sector Count : 1 #1 to 5 sectors for this slave Data Link Address : 1 #Range is 0 to 65535 DL address of slave # This section defined if Unbalanced mode utilized Failure Delay : 10 #Min Sec to delay before poll of offline slave #(0 to 2000) (Unbalanced only) Confirm Timeout : 1000 #0 to 2^32-1 mSec to wait for DL confirm Retry Count : 2 #0 to 255 retries for if no confirm #Parameters used for unbalanced mode of operation C1/C2 Poll Count Pend : 10 #class 1 or 2 polls before next slave tried (0-65535) Class 1 Polls : 5 #Max class 1 polls to this session Class 1 Pend delay : 10 #Min mSec delay between call (0 to 2^32-1) Class 2 Pend delay : 10 #Min mSec delay between call (0 to 2^32-1) Class 1 Poll delay : 10 #Min mSec delay between call (0 to 2^32-1) Class 2 Poll delay : 10 #Min mSec delay between call (0 to 2^32-1) Auto Clock Req Mode : 0 #0=Sync Only, 1=Load delay/sync, #2=Aquire delay/load delay/sync Propagation Delay : 0 #Fixed time delay for clock sync (0-65535) Response Timeout : 1000 #Timeout for confirm of req (0 to 2^32-1) ACTTERM with setpoint : Y #Y=ACTTERM last response from setpoint cmd #N=ACTCON last response from setpoint cmd [IEC-103 Master Session 0 Sector 0] Common ASDU Address : 3 #Range 0 to 255 Sector address #Req init requests when session first online (not req if slave sends # EOI sequence) Online Time sync : Y #Send time sync message when first online Online General Int : Y #Send general interrogation #Req init requests when EOI (end of initialization) received from slave EOI Time sync : Y #Send time sync message when first online EOI General Int : Y #Send general interrogation # Database definition for this session/sector # Types are as follows: # # Monitored ASDU Types # 1 = Time-tagged message (bit addressed with 2 bits/point) # 2 = Time-tagged message with relative time (bit addressed with 2 bits/point) # 3 = Measurands I (4 word values using word address using double-word address) # 4 = Time-tagged measurands with relative time (1 float value) # 5 = Identification (12 characters using a byte address) # 9 = Measurands II (9 word values using word address) #205= Siemens Meter Data (Private Range) # # Point Index = Database address in module # ASDU Index Description # 1 Bit address with each point occupying 2 bits # 2 Bit address with each point occupying 2 bits # 3 Word address with each point occupying 4 words # 4 Double-word address for the single float value # 5 Byte address with each point occupying 12 bytes # 9 Word address with each point occupying 9 words # 205 Double-word address for each meter point # # Function Code Values # Code Definition # 128 Distance protection # 160 Overcurrent protection # 176 Transformer differential protection # 192 Line Differential protection # 255 Global function type # # Database Point is the information object address in the slave unit. # # ASDU Database Function Point = Information # Type Index Code Index Number START 1 0 128 16 #Database bit-address 0 1 2 128 17 #Database bit-address 2 1 4 128 18 #Database bit-address 4 1 6 128 19 #Database bit-address 6 1 8 128 20 #Database bit-address 8 2 10 128 64 #Database bit-address 10 2 12 128 65 #Database bit-address 12 2 14 128 66 #Database bit-address 14 3 10 128 144 #Database word-address 10 3 11 128 145 #Database word-address 11 3 12 128 146 #Database word-address 12 3 13 128 147 #Database word-address 13 4 15 128 73 #Database double-word address 15 = Database word address 30 5 80 128 5 #Database byte address 80 9 60 128 148 #Database word-address 60 205 1800 133 51 END [IEC-103 Master Session 0 Sector 1] Common ASDU Address : 4 #Range 0 to 255 Sector address #Req init requests when session first online (not req if slave sends # EOI sequence) Online Time sync : Y #Send time sync message when first online Online General Int : Y #Send general interrogation #Req init requests when EOI (end of initialization) received from slave EOI Time sync : Y #Send time sync message when first online EOI General Int : Y #Send general interrogation # Database definition for this session/sector # # Database Point is the information object address in the slave unit. # # ASDU Database Function Point = Information # Type Index Code Index Number START END [IEC-103 Master Session 0 Sector 2] Common ASDU Address : 5 #Range 0 to 255 Sector address #Req init requests when session first online (not req if slave sends # EOI sequence) Online Time sync : Y #Send time sync message when first online Online General Int : Y #Send general interrogation #Req init requests when EOI (end of initialization) received from slave EOI Time sync : Y #Send time sync message when first online EOI General Int : Y #Send general interrogation # Database definition for this session/sector # # Database Point is the information object address in the slave unit. # # ASDU Database Function Point = Information # Type Index Code Index Number START END # This section is used to define session 0 which runs on Port 1 [IEC-103 Master Session 1] Communication Port : 1 #Index of COM port for session (0) Sector Count : 1 #1 to 5 sectors for this slave Data Link Address : 2 #Range is 0 to 65535 DL address of slave # This section defined if Unbalanced mode utilized Failure Delay : 10 #Min Sec to delay before poll of offline slave #(0 to 2000) (Unbalanced only) Confirm Timeout : 1000 #0 to 2^32-1 mSec to wait for DL confirm Retry Count : 2 #0 to 255 retries for if no confirm #Parameters used for unbalanced mode of operation C1/C2 Poll Count Pend : 10 #class 1 or 2 polls before next slave tried (0-65535) Class 1 Polls : 5 #Max class 1 polls to this session Class 1 Pend delay : 10 #Min mSec delay between call (0 to 2^32-1) Class 2 Pend delay : 10 #Min mSec delay between call (0 to 2^32-1) Class 1 Poll delay : 10 #Min mSec delay between call (0 to 2^32-1) Class 2 Poll delay : 10 #Min mSec delay between call (0 to 2^32-1) Auto Clock Req Mode : 0 #0=Sync Only, 1=Load delay/sync, #2=Aquire delay/load delay/sync Propagation Delay : 0 #Fixed time delay for clock sync (0-65535) Response Timeout : 1000 #Timeout for confirm of req (0 to 2^32-1) ACTTERM with setpoint : Y #Y=ACTTERM last response from setpoint cmd #N=ACTCON last response from setpoint cmd [IEC-103 Master Session 1 Sector 0] Common ASDU Address : 4 #Range 0 to 65534 Sector address #Req init requests when session first online (not req if slave sends # EOI sequence) Online Time sync : Y #Send time sync message when first online Online General Int : Y #Send general interrogation #Req init requests when EOI (end of initialization) received from slave EOI Time sync : Y #Send time sync message when first online EOI General Int : Y #Send general interrogation # Database definition for this session/sector # # ASDU Database Function Point # Type Index Code Index START END [IEC-103 Master Session 1 Sector 1] Common ASDU Address : 3 #Range 0 to 255 Sector address #Req init requests when session first online (not req if slave sends # EOI sequence) Online Time sync : Y #Send time sync message when first online Online General Int : Y #Send general interrogation #Req init requests when EOI (end of initialization) received from slave EOI Time sync : Y #Send time sync message when first online EOI General Int : Y #Send general interrogation # Database definition for this session/sector # # Database Point is the information object address in the slave unit. # # ASDU Database Function Point = Information # Type Index Code Index Number START END [IEC-103 Master Session 1 Sector 2] Common ASDU Address : 3 #Range 0 to 255 Sector address #Req init requests when session first online (not req if slave sends # EOI sequence) Online Time sync : Y #Send time sync message when first online Online General Int : Y #Send general interrogation #Req init requests when EOI (end of initialization) received from slave EOI Time sync : Y #Send time sync message when first online EOI General Int : Y #Send general interrogation # Database definition for this session/sector # # Database Point is the information object address in the slave unit. # # ASDU Database Function Point = Information # Type Index Code Index Number START END # This section is used to define session 2 which runs on Port 0 [IEC-103 Master Session 2] Communication Port : 0 #Index of COM port for session (0) Sector Count : 3 #1 to 5 sectors for this slave Data Link Address : 3 #Range is 0 to 65535 DL address of slave # This section defined if Unbalanced mode utilized Failure Delay : 10 #Min Sec to delay before poll of offline slave #(0 to 2000) (Unbalanced only) Confirm Timeout : 1000 #0 to 2^32-1 mSec to wait for DL confirm Retry Count : 2 #0 to 255 retries for if no confirm #Parameters used for unbalanced mode of operation C1/C2 Poll Count Pend : 10 #class 1 or 2 polls before next slave tried (0-65535) Class 1 Polls : 5 #Max class 1 polls to this session Class 1 Pend delay : 0 #Min mSec delay between call (0 to 2^32-1) Class 2 Pend delay : 0 #Min mSec delay between call (0 to 2^32-1) Class 1 Poll delay : 0 #Min mSec delay between call (0 to 2^32-1) Class 2 Poll delay : 200 #Min mSec delay between call (0 to 2^32-1) Auto Clock Req Mode : 0 #0=Sync Only, 1=Load delay/sync, #2=Aquire delay/load delay/sync Propagation Delay : 0 #Fixed time delay for clock sync (0-65535) Response Timeout : 1000 #Timeout for confirm of req (0 to 2^32-1) ACTTERM with setpoint : Y #Y=ACTTERM last response from setpoint cmd #N=ACTCON last response from setpoint cmd [IEC-103 Master Session 2 Sector 0] Common ASDU Address : 5 #Range 0 to 255 Sector address #Req init requests when session first online (not req if slave sends # EOI sequence) Online Time sync : N #Send time sync message when first online Online General Int : N #Send general interrogation #Req init requests when EOI (end of initialization) received from slave EOI Time sync : Y #Send time sync message when first online EOI General Int : Y #Send general interrogation # Database definition for this session/sector # Types are as follows: # # Monitored ASDU Types # 1 = Time-tagged message (bit addressed with 2 bits/point) # 2 = Time-tagged message with relative time (bit addressed with 2 bits/point) # 3 = Measurands I (4 word values using word address using double-word address) # 4 = Time-tagged measurands with relative time (1 float value) # 5 = Identification (12 characters using a byte address) # 9 = Measurands II (9 word values using word address) #205= Siemens Meter Data (Private Range) # # Point Index = Database address in module # ASDU Index Description # 1 Bit address with each point occupying 2 bits # 2 Bit address with each point occupying 2 bits # 3 Word address with each point occupying 4 words # 4 Double-word address for the single float value # 5 Byte address with each point occupying 12 bytes # 9 Word address with each point occupying 9 words # 205 Double-word address for each meter point # # Function Code Values # Code Definition # 128 Distance protection # 160 Overcurrent protection # 176 Transformer differential protection # 192 Line Differential protection # 255 Global function type # # Database Point is the information object address in the slave unit. # # ASDU Point Function Database # Type Index Code Point START END [IEC-103 Master Session 2 Sector 1] Common ASDU Address : 6 #Range 0 to 255 Sector address #Req init requests when session first online (not req if slave sends # EOI sequence) Online Time sync : N #Send time sync message when first online Online General Int : N #Send general interrogation #Req init requests when EOI (end of initialization) received from slave EOI Time sync : Y #Send time sync message when first online EOI General Int : Y #Send general interrogation # Database definition for this session/sector # Types are as follows: # # Monitored ASDU Types # 1 = Time-tagged message (bit addressed with 2 bits/point) # 2 = Time-tagged message with relative time (bit addressed with 2 bits/point) # 3 = Measurands I (4 word values using word address using double-word address) # 4 = Time-tagged measurands with relative time (1 float value) # 5 = Identification (12 characters using a byte address) # 9 = Measurands II (9 word values using word address) #205= Siemens Meter Data (Private Range) # # Point Index = Database address in module # ASDU Index Description # 1 Bit address with each point occupying 2 bits # 2 Bit address with each point occupying 2 bits # 3 Word address with each point occupying 4 words # 4 Double-word address for the single float value # 5 Byte address with each point occupying 12 bytes # 9 Word address with each point occupying 9 words # 205 Double-word address for each meter point # # Function Code Values # Code Definition # 128 Distance protection # 160 Overcurrent protection # 176 Transformer differential protection # 192 Line Differential protection # 255 Global function type # # Database Point is the information object address in the slave unit. # # ASDU Point Function Database # Type Index Code Point START END [IEC-103 Master Session 2 Sector 2] Common ASDU Address : 7 #Range 0 to 255 Sector address #Req init requests when session first online (not req if slave sends # EOI sequence) Online Time sync : Y #Send time sync message when first online Online General Int : Y #Send general interrogation #Req init requests when EOI (end of initialization) received from slave EOI Time sync : Y #Send time sync message when first online EOI General Int : Y #Send general interrogation # Database definition for this session/sector # Types are as follows: # # Monitored ASDU Types # 1 = Time-tagged message (bit addressed with 2 bits/point) # 2 = Time-tagged message with relative time (bit addressed with 2 bits/point) # 3 = Measurands I (4 word values using word address using double-word address) # 4 = Time-tagged measurands with relative time (1 float value) # 5 = Identification (12 characters using a byte address) # 9 = Measurands II (9 word values using word address) #205= Siemens Meter Data (Private Range) # # Point Index = Database address in module # ASDU Index Description # 1 Bit address with each point occupying 2 bits # 2 Bit address with each point occupying 2 bits # 3 Word address with each point occupying 4 words # 4 Double-word address for the single float value # 5 Byte address with each point occupying 12 bytes # 9 Word address with each point occupying 9 words # 205 Double-word address for each meter point # # Function Code Values # Code Definition # 128 Distance protection # 160 Overcurrent protection # 176 Transformer differential protection # 192 Line Differential protection # 255 Global function type # # Database Point is the information object address in the slave unit. # # ASDU Point Function Database # Type Index Code Point START END # This section is used to define session 3 which runs on Port 0 [IEC-103 Master Session 3] Communication Port : 0 #Index of COM port for session (0) Sector Count : 3 #1 to 5 sectors for this slave Data Link Address : 4 #Range is 0 to 65535 DL address of slave # This section defined if Unbalanced mode utilized Failure Delay : 10 #Min Sec to delay before poll of offline slave #(0 to 2000) (Unbalanced only) Confirm Timeout : 1000 #0 to 2^32-1 mSec to wait for DL confirm Retry Count : 2 #0 to 255 retries for if no confirm #Parameters used for unbalanced mode of operation C1/C2 Poll Count Pend : 10 #class 1 or 2 polls before next slave tried (0-65535) Class 1 Polls : 5 #Max class 1 polls to this session Class 1 Pend delay : 0 #Min mSec delay between call (0 to 2^32-1) Class 2 Pend delay : 0 #Min mSec delay between call (0 to 2^32-1) Class 1 Poll delay : 0 #Min mSec delay between call (0 to 2^32-1) Class 2 Poll delay : 200 #Min mSec delay between call (0 to 2^32-1) Auto Clock Req Mode : 0 #0=Sync Only, 1=Load delay/sync, #2=Aquire delay/load delay/sync Propagation Delay : 0 #Fixed time delay for clock sync (0-65535) Response Timeout : 1000 #Timeout for confirm of req (0 to 2^32-1) ACTTERM with setpoint : Y #Y=ACTTERM last response from setpoint cmd #N=ACTCON last response from setpoint cmd [IEC-103 Master Session 3 Sector 0] Common ASDU Address : 5 #Range 0 to 255 Sector address #Req init requests when session first online (not req if slave sends # EOI sequence) Online Time sync : N #Send time sync message when first online Online General Int : N #Send general interrogation #Req init requests when EOI (end of initialization) received from slave EOI Time sync : Y #Send time sync message when first online EOI General Int : Y #Send general interrogation # Database definition for this session/sector # Types are as follows: # # Monitored ASDU Types # 1 = Time-tagged message (bit addressed with 2 bits/point) # 2 = Time-tagged message with relative time (bit addressed with 2 bits/point) # 3 = Measurands I (4 word values using word address using double-word address) # 4 = Time-tagged measurands with relative time (1 float value) # 5 = Identification (12 characters using a byte address) # 9 = Measurands II (9 word values using word address) #205= Siemens Meter Data (Private Range) # # Point Index = Database address in module # ASDU Index Description # 1 Bit address with each point occupying 2 bits # 2 Bit address with each point occupying 2 bits # 3 Word address with each point occupying 4 words # 4 Double-word address for the single float value # 5 Byte address with each point occupying 12 bytes # 9 Word address with each point occupying 9 words # 205 Double-word address for each meter point # # Function Code Values # Code Definition # 128 Distance protection # 160 Overcurrent protection # 176 Transformer differential protection # 192 Line Differential protection # 255 Global function type # # Database Point is the information object address in the slave unit. # # ASDU Point Function Database # Type Index Code Point START END [IEC-103 Master Session 3 Sector 1] Common ASDU Address : 6 #Range 0 to 255 Sector address #Req init requests when session first online (not req if slave sends # EOI sequence) Online Time sync : N #Send time sync message when first online Online General Int : N #Send general interrogation #Req init requests when EOI (end of initialization) received from slave EOI Time sync : Y #Send time sync message when first online EOI General Int : Y #Send general interrogation # Database definition for this session/sector # Types are as follows: # # Monitored ASDU Types # 1 = Time-tagged message (bit addressed with 2 bits/point) # 2 = Time-tagged message with relative time (bit addressed with 2 bits/point) # 3 = Measurands I (4 word values using word address using double-word address) # 4 = Time-tagged measurands with relative time (1 float value) # 5 = Identification (12 characters using a byte address) # 9 = Measurands II (9 word values using word address) #205= Siemens Meter Data (Private Range) # # Point Index = Database address in module # ASDU Index Description # 1 Bit address with each point occupying 2 bits # 2 Bit address with each point occupying 2 bits # 3 Word address with each point occupying 4 words # 4 Double-word address for the single float value # 5 Byte address with each point occupying 12 bytes # 9 Word address with each point occupying 9 words # 205 Double-word address for each meter point # # Function Code Values # Code Definition # 128 Distance protection # 160 Overcurrent protection # 176 Transformer differential protection # 192 Line Differential protection # 255 Global function type # # Database Point is the information object address in the slave unit. # # ASDU Point Function Database # Type Index Code Point START END [IEC-103 Master Session 3 Sector 2] Common ASDU Address : 7 #Range 0 to 255 Sector address #Req init requests when session first online (not req if slave sends # EOI sequence) Online Time sync : Y #Send time sync message when first online Online General Int : Y #Send general interrogation #Req init requests when EOI (end of initialization) received from slave EOI Time sync : Y #Send time sync message when first online EOI General Int : Y #Send general interrogation # Database definition for this session/sector # Types are as follows: # # Monitored ASDU Types # 1 = Time-tagged message (bit addressed with 2 bits/point) # 2 = Time-tagged message with relative time (bit addressed with 2 bits/point) # 3 = Measurands I (4 word values using word address using double-word address) # 4 = Time-tagged measurands with relative time (1 float value) # 5 = Identification (12 characters using a byte address) # 9 = Measurands II (9 word values using word address) #205= Siemens Meter Data (Private Range) # # Point Index = Database address in module # ASDU Index Description # 1 Bit address with each point occupying 2 bits # 2 Bit address with each point occupying 2 bits # 3 Word address with each point occupying 4 words # 4 Double-word address for the single float value # 5 Byte address with each point occupying 12 bytes # 9 Word address with each point occupying 9 words # 205 Double-word address for each meter point # # Function Code Values # Code Definition # 128 Distance protection # 160 Overcurrent protection # 176 Transformer differential protection # 192 Line Differential protection # 255 Global function type # # Database Point is the information object address in the slave unit. # # ASDU Point Function Database # Type Index Code Point START END # This section is used to define session 4 which runs on Port 0 [IEC-103 Master Session 4] Communication Port : 0 #Index of COM port for session (0) Sector Count : 3 #1 to 5 sectors for this slave Data Link Address : 5 #Range is 0 to 65535 DL address of slave # This section defined if Unbalanced mode utilized Failure Delay : 10 #Min Sec to delay before poll of offline slave #(0 to 2000) (Unbalanced only) Confirm Timeout : 1000 #0 to 2^32-1 mSec to wait for DL confirm Retry Count : 2 #0 to 255 retries for if no confirm #Parameters used for unbalanced mode of operation C1/C2 Poll Count Pend : 10 #class 1 or 2 polls before next slave tried (0-65535) Class 1 Polls : 5 #Max class 1 polls to this session Class 1 Pend delay : 0 #Min mSec delay between call (0 to 2^32-1) Class 2 Pend delay : 0 #Min mSec delay between call (0 to 2^32-1) Class 1 Poll delay : 0 #Min mSec delay between call (0 to 2^32-1) Class 2 Poll delay : 200 #Min mSec delay between call (0 to 2^32-1) Auto Clock Req Mode : 0 #0=Sync Only, 1=Load delay/sync, #2=Aquire delay/load delay/sync Propagation Delay : 0 #Fixed time delay for clock sync (0-65535) Response Timeout : 1000 #Timeout for confirm of req (0 to 2^32-1) ACTTERM with setpoint : Y #Y=ACTTERM last response from setpoint cmd #N=ACTCON last response from setpoint cmd [IEC-103 Master Session 4 Sector 0] Common ASDU Address : 5 #Range 0 to 255 Sector address #Req init requests when session first online (not req if slave sends # EOI sequence) Online Time sync : N #Send time sync message when first online Online General Int : N #Send general interrogation #Req init requests when EOI (end of initialization) received from slave EOI Time sync : Y #Send time sync message when first online EOI General Int : Y #Send general interrogation # Database definition for this session/sector # Types are as follows: # # Monitored ASDU Types # 1 = Time-tagged message (bit addressed with 2 bits/point) # 2 = Time-tagged message with relative time (bit addressed with 2 bits/point) # 3 = Measurands I (4 word values using word address using double-word address) # 4 = Time-tagged measurands with relative time (1 float value) # 5 = Identification (12 characters using a byte address) # 9 = Measurands II (9 word values using word address) #205= Siemens Meter Data (Private Range) # # Point Index = Database address in module # ASDU Index Description # 1 Bit address with each point occupying 2 bits # 2 Bit address with each point occupying 2 bits # 3 Word address with each point occupying 4 words # 4 Double-word address for the single float value # 5 Byte address with each point occupying 12 bytes # 9 Word address with each point occupying 9 words # 205 Double-word address for each meter point # # Function Code Values # Code Definition # 128 Distance protection # 160 Overcurrent protection # 176 Transformer differential protection # 192 Line Differential protection # 255 Global function type # # Database Point is the information object address in the slave unit. # # ASDU Point Function Database # Type Index Code Point START END [IEC-103 Master Session 4 Sector 1] Common ASDU Address : 6 #Range 0 to 255 Sector address #Req init requests when session first online (not req if slave sends # EOI sequence) Online Time sync : N #Send time sync message when first online Online General Int : N #Send general interrogation #Req init requests when EOI (end of initialization) received from slave EOI Time sync : Y #Send time sync message when first online EOI General Int : Y #Send general interrogation # Database definition for this session/sector # Types are as follows: # # Monitored ASDU Types # 1 = Time-tagged message (bit addressed with 2 bits/point) # 2 = Time-tagged message with relative time (bit addressed with 2 bits/point) # 3 = Measurands I (4 word values using word address using double-word address) # 4 = Time-tagged measurands with relative time (1 float value) # 5 = Identification (12 characters using a byte address) # 9 = Measurands II (9 word values using word address) #205= Siemens Meter Data (Private Range) # # Point Index = Database address in module # ASDU Index Description # 1 Bit address with each point occupying 2 bits # 2 Bit address with each point occupying 2 bits # 3 Word address with each point occupying 4 words # 4 Double-word address for the single float value # 5 Byte address with each point occupying 12 bytes # 9 Word address with each point occupying 9 words # 205 Double-word address for each meter point # # Function Code Values # Code Definition # 128 Distance protection # 160 Overcurrent protection # 176 Transformer differential protection # 192 Line Differential protection # 255 Global function type # # Database Point is the information object address in the slave unit. # # ASDU Point Function Database # Type Index Code Point START END [IEC-103 Master Session 4 Sector 2] Common ASDU Address : 7 #Range 0 to 255 Sector address #Req init requests when session first online (not req if slave sends # EOI sequence) Online Time sync : Y #Send time sync message when first online Online General Int : Y #Send general interrogation #Req init requests when EOI (end of initialization) received from slave EOI Time sync : Y #Send time sync message when first online EOI General Int : Y #Send general interrogation # Database definition for this session/sector # Types are as follows: # # Monitored ASDU Types # 1 = Time-tagged message (bit addressed with 2 bits/point) # 2 = Time-tagged message with relative time (bit addressed with 2 bits/point) # 3 = Measurands I (4 word values using word address using double-word address) # 4 = Time-tagged measurands with relative time (1 float value) # 5 = Identification (12 characters using a byte address) # 9 = Measurands II (9 word values using word address) #205= Siemens Meter Data (Private Range) # # Point Index = Database address in module # ASDU Index Description # 1 Bit address with each point occupying 2 bits # 2 Bit address with each point occupying 2 bits # 3 Word address with each point occupying 4 words # 4 Double-word address for the single float value # 5 Byte address with each point occupying 12 bytes # 9 Word address with each point occupying 9 words # 205 Double-word address for each meter point # # Function Code Values # Code Definition # 128 Distance protection # 160 Overcurrent protection # 176 Transformer differential protection # 192 Line Differential protection # 255 Global function type # # Database Point is the information object address in the slave unit. # # ASDU Point Function Database # Type Index Code Point START END # This section is used to define session 5 which runs on Port 0 [IEC-103 Master Session 5] Communication Port : 0 #Index of COM port for session (0) Sector Count : 3 #1 to 5 sectors for this slave Data Link Address : 6 #Range is 0 to 65535 DL address of slave # This section defined if Unbalanced mode utilized Failure Delay : 10 #Min Sec to delay before poll of offline slave #(0 to 2000) (Unbalanced only) Confirm Timeout : 1000 #0 to 2^32-1 mSec to wait for DL confirm Retry Count : 2 #0 to 255 retries for if no confirm #Parameters used for unbalanced mode of operation C1/C2 Poll Count Pend : 10 #class 1 or 2 polls before next slave tried (0-65535) Class 1 Polls : 5 #Max class 1 polls to this session Class 1 Pend delay : 0 #Min mSec delay between call (0 to 2^32-1) Class 2 Pend delay : 0 #Min mSec delay between call (0 to 2^32-1) Class 1 Poll delay : 0 #Min mSec delay between call (0 to 2^32-1) Class 2 Poll delay : 200 #Min mSec delay between call (0 to 2^32-1) Auto Clock Req Mode : 0 #0=Sync Only, 1=Load delay/sync, #2=Aquire delay/load delay/sync Propagation Delay : 0 #Fixed time delay for clock sync (0-65535) Response Timeout : 1000 #Timeout for confirm of req (0 to 2^32-1) ACTTERM with setpoint : Y #Y=ACTTERM last response from setpoint cmd #N=ACTCON last response from setpoint cmd [IEC-103 Master Session 5 Sector 0] Common ASDU Address : 5 #Range 0 to 255 Sector address #Req init requests when session first online (not req if slave sends # EOI sequence) Online Time sync : N #Send time sync message when first online Online General Int : N #Send general interrogation #Req init requests when EOI (end of initialization) received from slave EOI Time sync : Y #Send time sync message when first online EOI General Int : Y #Send general interrogation # Database definition for this session/sector # Types are as follows: # # Monitored ASDU Types # 1 = Time-tagged message (bit addressed with 2 bits/point) # 2 = Time-tagged message with relative time (bit addressed with 2 bits/point) # 3 = Measurands I (4 word values using word address using double-word address) # 4 = Time-tagged measurands with relative time (1 float value) # 5 = Identification (12 characters using a byte address) # 9 = Measurands II (9 word values using word address) #205= Siemens Meter Data (Private Range) # # Point Index = Database address in module # ASDU Index Description # 1 Bit address with each point occupying 2 bits # 2 Bit address with each point occupying 2 bits # 3 Word address with each point occupying 4 words # 4 Double-word address for the single float value # 5 Byte address with each point occupying 12 bytes # 9 Word address with each point occupying 9 words # 205 Double-word address for each meter point # # Function Code Values # Code Definition # 128 Distance protection # 160 Overcurrent protection # 176 Transformer differential protection # 192 Line Differential protection # 255 Global function type # # Database Point is the information object address in the slave unit. # # ASDU Point Function Database # Type Index Code Point START END [IEC-103 Master Session 5 Sector 1] Common ASDU Address : 6 #Range 0 to 255 Sector address #Req init requests when session first online (not req if slave sends # EOI sequence) Online Time sync : N #Send time sync message when first online Online General Int : N #Send general interrogation #Req init requests when EOI (end of initialization) received from slave EOI Time sync : Y #Send time sync message when first online EOI General Int : Y #Send general interrogation # Database definition for this session/sector # Types are as follows: # # Monitored ASDU Types # 1 = Time-tagged message (bit addressed with 2 bits/point) # 2 = Time-tagged message with relative time (bit addressed with 2 bits/point) # 3 = Measurands I (4 word values using word address using double-word address) # 4 = Time-tagged measurands with relative time (1 float value) # 5 = Identification (12 characters using a byte address) # 9 = Measurands II (9 word values using word address) #205= Siemens Meter Data (Private Range) # # Point Index = Database address in module # ASDU Index Description # 1 Bit address with each point occupying 2 bits # 2 Bit address with each point occupying 2 bits # 3 Word address with each point occupying 4 words # 4 Double-word address for the single float value # 5 Byte address with each point occupying 12 bytes # 9 Word address with each point occupying 9 words # 205 Double-word address for each meter point # # Function Code Values # Code Definition # 128 Distance protection # 160 Overcurrent protection # 176 Transformer differential protection # 192 Line Differential protection # 255 Global function type # # Database Point is the information object address in the slave unit. # # ASDU Point Function Database # Type Index Code Point START END [IEC-103 Master Session 5 Sector 2] Common ASDU Address : 7 #Range 0 to 255 Sector address #Req init requests when session first online (not req if slave sends # EOI sequence) Online Time sync : Y #Send time sync message when first online Online General Int : Y #Send general interrogation #Req init requests when EOI (end of initialization) received from slave EOI Time sync : Y #Send time sync message when first online EOI General Int : Y #Send general interrogation # Database definition for this session/sector # Types are as follows: # # Monitored ASDU Types # 1 = Time-tagged message (bit addressed with 2 bits/point) # 2 = Time-tagged message with relative time (bit addressed with 2 bits/point) # 3 = Measurands I (4 word values using word address using double-word address) # 4 = Time-tagged measurands with relative time (1 float value) # 5 = Identification (12 characters using a byte address) # 9 = Measurands II (9 word values using word address) #205= Siemens Meter Data (Private Range) # # Point Index = Database address in module # ASDU Index Description # 1 Bit address with each point occupying 2 bits # 2 Bit address with each point occupying 2 bits # 3 Word address with each point occupying 4 words # 4 Double-word address for the single float value # 5 Byte address with each point occupying 12 bytes # 9 Word address with each point occupying 9 words # 205 Double-word address for each meter point # # Function Code Values # Code Definition # 128 Distance protection # 160 Overcurrent protection # 176 Transformer differential protection # 192 Line Differential protection # 255 Global function type # # Database Point is the information object address in the slave unit. # # ASDU Point Function Database # Type Index Code Point START END # This section is used to define session 6 which runs on Port 0 [IEC-103 Master Session 6] Communication Port : 0 #Index of COM port for session (0) Sector Count : 3 #1 to 5 sectors for this slave Data Link Address : 7 #Range is 0 to 65535 DL address of slave # This section defined if Unbalanced mode utilized Failure Delay : 10 #Min Sec to delay before poll of offline slave #(0 to 2000) (Unbalanced only) Confirm Timeout : 1000 #0 to 2^32-1 mSec to wait for DL confirm Retry Count : 2 #0 to 255 retries for if no confirm #Parameters used for unbalanced mode of operation C1/C2 Poll Count Pend : 10 #class 1 or 2 polls before next slave tried (0-65535) Class 1 Polls : 5 #Max class 1 polls to this session Class 1 Pend delay : 0 #Min mSec delay between call (0 to 2^32-1) Class 2 Pend delay : 0 #Min mSec delay between call (0 to 2^32-1) Class 1 Poll delay : 0 #Min mSec delay between call (0 to 2^32-1) Class 2 Poll delay : 200 #Min mSec delay between call (0 to 2^32-1) Auto Clock Req Mode : 0 #0=Sync Only, 1=Load delay/sync, #2=Aquire delay/load delay/sync Propagation Delay : 0 #Fixed time delay for clock sync (0-65535) Response Timeout : 1000 #Timeout for confirm of req (0 to 2^32-1) ACTTERM with setpoint : Y #Y=ACTTERM last response from setpoint cmd #N=ACTCON last response from setpoint cmd [IEC-103 Master Session 6 Sector 0] Common ASDU Address : 5 #Range 0 to 255 Sector address #Req init requests when session first online (not req if slave sends # EOI sequence) Online Time sync : N #Send time sync message when first online Online General Int : N #Send general interrogation #Req init requests when EOI (end of initialization) received from slave EOI Time sync : Y #Send time sync message when first online EOI General Int : Y #Send general interrogation # Database definition for this session/sector # Types are as follows: # # Monitored ASDU Types # 1 = Time-tagged message (bit addressed with 2 bits/point) # 2 = Time-tagged message with relative time (bit addressed with 2 bits/point) # 3 = Measurands I (4 word values using word address using double-word address) # 4 = Time-tagged measurands with relative time (1 float value) # 5 = Identification (12 characters using a byte address) # 9 = Measurands II (9 word values using word address) #205= Siemens Meter Data (Private Range) # # Point Index = Database address in module # ASDU Index Description # 1 Bit address with each point occupying 2 bits # 2 Bit address with each point occupying 2 bits # 3 Word address with each point occupying 4 words # 4 Double-word address for the single float value # 5 Byte address with each point occupying 12 bytes # 9 Word address with each point occupying 9 words # 205 Double-word address for each meter point # # Function Code Values # Code Definition # 128 Distance protection # 160 Overcurrent protection # 176 Transformer differential protection # 192 Line Differential protection # 255 Global function type # # Database Point is the information object address in the slave unit. # # ASDU Point Function Database # Type Index Code Point START END [IEC-103 Master Session 6 Sector 1] Common ASDU Address : 6 #Range 0 to 255 Sector address #Req init requests when session first online (not req if slave sends # EOI sequence) Online Time sync : N #Send time sync message when first online Online General Int : N #Send general interrogation #Req init requests when EOI (end of initialization) received from slave EOI Time sync : Y #Send time sync message when first online EOI General Int : Y #Send general interrogation # Database definition for this session/sector # Types are as follows: # # Monitored ASDU Types # 1 = Time-tagged message (bit addressed with 2 bits/point) # 2 = Time-tagged message with relative time (bit addressed with 2 bits/point) # 3 = Measurands I (4 word values using word address using double-word address) # 4 = Time-tagged measurands with relative time (1 float value) # 5 = Identification (12 characters using a byte address) # 9 = Measurands II (9 word values using word address) #205= Siemens Meter Data (Private Range) # # Point Index = Database address in module # ASDU Index Description # 1 Bit address with each point occupying 2 bits # 2 Bit address with each point occupying 2 bits # 3 Word address with each point occupying 4 words # 4 Double-word address for the single float value # 5 Byte address with each point occupying 12 bytes # 9 Word address with each point occupying 9 words # 205 Double-word address for each meter point # # Function Code Values # Code Definition # 128 Distance protection # 160 Overcurrent protection # 176 Transformer differential protection # 192 Line Differential protection # 255 Global function type # # Database Point is the information object address in the slave unit. # # ASDU Point Function Database # Type Index Code Point START END [IEC-103 Master Session 6 Sector 2] Common ASDU Address : 7 #Range 0 to 255 Sector address #Req init requests when session first online (not req if slave sends # EOI sequence) Online Time sync : Y #Send time sync message when first online Online General Int : Y #Send general interrogation #Req init requests when EOI (end of initialization) received from slave EOI Time sync : Y #Send time sync message when first online EOI General Int : Y #Send general interrogation # Database definition for this session/sector # Types are as follows: # # Monitored ASDU Types # 1 = Time-tagged message (bit addressed with 2 bits/point) # 2 = Time-tagged message with relative time (bit addressed with 2 bits/point) # 3 = Measurands I (4 word values using word address using double-word address) # 4 = Time-tagged measurands with relative time (1 float value) # 5 = Identification (12 characters using a byte address) # 9 = Measurands II (9 word values using word address) #205= Siemens Meter Data (Private Range) # # Point Index = Database address in module # ASDU Index Description # 1 Bit address with each point occupying 2 bits # 2 Bit address with each point occupying 2 bits # 3 Word address with each point occupying 4 words # 4 Double-word address for the single float value # 5 Byte address with each point occupying 12 bytes # 9 Word address with each point occupying 9 words # 205 Double-word address for each meter point # # Function Code Values # Code Definition # 128 Distance protection # 160 Overcurrent protection # 176 Transformer differential protection # 192 Line Differential protection # 255 Global function type # # Database Point is the information object address in the slave unit. # # ASDU Point Function Database # Type Index Code Point START END # This section is used to define session 7 which runs on Port 0 [IEC-103 Master Session 7] Communication Port : 0 #Index of COM port for session (0) Sector Count : 3 #1 to 5 sectors for this slave Data Link Address : 8 #Range is 0 to 65535 DL address of slave # This section defined if Unbalanced mode utilized Failure Delay : 10 #Min Sec to delay before poll of offline slave #(0 to 2000) (Unbalanced only) Confirm Timeout : 1000 #0 to 2^32-1 mSec to wait for DL confirm Retry Count : 2 #0 to 255 retries for if no confirm #Parameters used for unbalanced mode of operation C1/C2 Poll Count Pend : 10 #class 1 or 2 polls before next slave tried (0-65535) Class 1 Polls : 5 #Max class 1 polls to this session Class 1 Pend delay : 0 #Min mSec delay between call (0 to 2^32-1) Class 2 Pend delay : 0 #Min mSec delay between call (0 to 2^32-1) Class 1 Poll delay : 0 #Min mSec delay between call (0 to 2^32-1) Class 2 Poll delay : 200 #Min mSec delay between call (0 to 2^32-1) Auto Clock Req Mode : 0 #0=Sync Only, 1=Load delay/sync, #2=Aquire delay/load delay/sync Propagation Delay : 0 #Fixed time delay for clock sync (0-65535) Response Timeout : 1000 #Timeout for confirm of req (0 to 2^32-1) ACTTERM with setpoint : Y #Y=ACTTERM last response from setpoint cmd #N=ACTCON last response from setpoint cmd [IEC-103 Master Session 7 Sector 0] Common ASDU Address : 5 #Range 0 to 255 Sector address #Req init requests when session first online (not req if slave sends # EOI sequence) Online Time sync : N #Send time sync message when first online Online General Int : N #Send general interrogation #Req init requests when EOI (end of initialization) received from slave EOI Time sync : Y #Send time sync message when first online EOI General Int : Y #Send general interrogation # Database definition for this session/sector # Types are as follows: # # Monitored ASDU Types # 1 = Time-tagged message (bit addressed with 2 bits/point) # 2 = Time-tagged message with relative time (bit addressed with 2 bits/point) # 3 = Measurands I (4 word values using word address using double-word address) # 4 = Time-tagged measurands with relative time (1 float value) # 5 = Identification (12 characters using a byte address) # 9 = Measurands II (9 word values using word address) #205= Siemens Meter Data (Private Range) # # Point Index = Database address in module # ASDU Index Description # 1 Bit address with each point occupying 2 bits # 2 Bit address with each point occupying 2 bits # 3 Word address with each point occupying 4 words # 4 Double-word address for the single float value # 5 Byte address with each point occupying 12 bytes # 9 Word address with each point occupying 9 words # 205 Double-word address for each meter point # # Function Code Values # Code Definition # 128 Distance protection # 160 Overcurrent protection # 176 Transformer differential protection # 192 Line Differential protection # 255 Global function type # # Database Point is the information object address in the slave unit. # # ASDU Point Function Database # Type Index Code Point START END [IEC-103 Master Session 7 Sector 1] Common ASDU Address : 6 #Range 0 to 255 Sector address #Req init requests when session first online (not req if slave sends # EOI sequence) Online Time sync : N #Send time sync message when first online Online General Int : N #Send general interrogation #Req init requests when EOI (end of initialization) received from slave EOI Time sync : Y #Send time sync message when first online EOI General Int : Y #Send general interrogation # Database definition for this session/sector # Types are as follows: # # Monitored ASDU Types # 1 = Time-tagged message (bit addressed with 2 bits/point) # 2 = Time-tagged message with relative time (bit addressed with 2 bits/point) # 3 = Measurands I (4 word values using word address using double-word address) # 4 = Time-tagged measurands with relative time (1 float value) # 5 = Identification (12 characters using a byte address) # 9 = Measurands II (9 word values using word address) #205= Siemens Meter Data (Private Range) # # Point Index = Database address in module # ASDU Index Description # 1 Bit address with each point occupying 2 bits # 2 Bit address with each point occupying 2 bits # 3 Word address with each point occupying 4 words # 4 Double-word address for the single float value # 5 Byte address with each point occupying 12 bytes # 9 Word address with each point occupying 9 words # 205 Double-word address for each meter point # # Function Code Values # Code Definition # 128 Distance protection # 160 Overcurrent protection # 176 Transformer differential protection # 192 Line Differential protection # 255 Global function type # # Database Point is the information object address in the slave unit. # # ASDU Point Function Database # Type Index Code Point START END [IEC-103 Master Session 7 Sector 2] Common ASDU Address : 7 #Range 0 to 255 Sector address #Req init requests when session first online (not req if slave sends # EOI sequence) Online Time sync : Y #Send time sync message when first online Online General Int : Y #Send general interrogation #Req init requests when EOI (end of initialization) received from slave EOI Time sync : Y #Send time sync message when first online EOI General Int : Y #Send general interrogation # Database definition for this session/sector # Types are as follows: # # Monitored ASDU Types # 1 = Time-tagged message (bit addressed with 2 bits/point) # 2 = Time-tagged message with relative time (bit addressed with 2 bits/point) # 3 = Measurands I (4 word values using word address using double-word address) # 4 = Time-tagged measurands with relative time (1 float value) # 5 = Identification (12 characters using a byte address) # 9 = Measurands II (9 word values using word address) #205= Siemens Meter Data (Private Range) # # Point Index = Database address in module # ASDU Index Description # 1 Bit address with each point occupying 2 bits # 2 Bit address with each point occupying 2 bits # 3 Word address with each point occupying 4 words # 4 Double-word address for the single float value # 5 Byte address with each point occupying 12 bytes # 9 Word address with each point occupying 9 words # 205 Double-word address for each meter point # # Function Code Values # Code Definition # 128 Distance protection # 160 Overcurrent protection # 176 Transformer differential protection # 192 Line Differential protection # 255 Global function type # # Database Point is the information object address in the slave unit. # # ASDU Point Function Database # Type Index Code Point START END # This section is used to define session 8 which runs on Port 0 [IEC-103 Master Session 8] Communication Port : 0 #Index of COM port for session (0) Sector Count : 3 #1 to 5 sectors for this slave Data Link Address : 9 #Range is 0 to 65535 DL address of slave # This section defined if Unbalanced mode utilized Failure Delay : 10 #Min Sec to delay before poll of offline slave #(0 to 2000) (Unbalanced only) Confirm Timeout : 1000 #0 to 2^32-1 mSec to wait for DL confirm Retry Count : 2 #0 to 255 retries for if no confirm #Parameters used for unbalanced mode of operation C1/C2 Poll Count Pend : 10 #class 1 or 2 polls before next slave tried (0-65535) Class 1 Polls : 5 #Max class 1 polls to this session Class 1 Pend delay : 0 #Min mSec delay between call (0 to 2^32-1) Class 2 Pend delay : 0 #Min mSec delay between call (0 to 2^32-1) Class 1 Poll delay : 0 #Min mSec delay between call (0 to 2^32-1) Class 2 Poll delay : 200 #Min mSec delay between call (0 to 2^32-1) Auto Clock Req Mode : 0 #0=Sync Only, 1=Load delay/sync, #2=Aquire delay/load delay/sync Propagation Delay : 0 #Fixed time delay for clock sync (0-65535) Response Timeout : 1000 #Timeout for confirm of req (0 to 2^32-1) ACTTERM with setpoint : Y #Y=ACTTERM last response from setpoint cmd #N=ACTCON last response from setpoint cmd [IEC-103 Master Session 8 Sector 0] Common ASDU Address : 5 #Range 0 to 255 Sector address #Req init requests when session first online (not req if slave sends # EOI sequence) Online Time sync : N #Send time sync message when first online Online General Int : N #Send general interrogation #Req init requests when EOI (end of initialization) received from slave EOI Time sync : Y #Send time sync message when first online EOI General Int : Y #Send general interrogation # Database definition for this session/sector # Types are as follows: # # Monitored ASDU Types # 1 = Time-tagged message (bit addressed with 2 bits/point) # 2 = Time-tagged message with relative time (bit addressed with 2 bits/point) # 3 = Measurands I (4 word values using word address using double-word address) # 4 = Time-tagged measurands with relative time (1 float value) # 5 = Identification (12 characters using a byte address) # 9 = Measurands II (9 word values using word address) #205= Siemens Meter Data (Private Range) # # Point Index = Database address in module # ASDU Index Description # 1 Bit address with each point occupying 2 bits # 2 Bit address with each point occupying 2 bits # 3 Word address with each point occupying 4 words # 4 Double-word address for the single float value # 5 Byte address with each point occupying 12 bytes # 9 Word address with each point occupying 9 words # 205 Double-word address for each meter point # # Function Code Values # Code Definition # 128 Distance protection # 160 Overcurrent protection # 176 Transformer differential protection # 192 Line Differential protection # 255 Global function type # # Database Point is the information object address in the slave unit. # # ASDU Point Function Database # Type Index Code Point START END [IEC-103 Master Session 8 Sector 1] Common ASDU Address : 6 #Range 0 to 255 Sector address #Req init requests when session first online (not req if slave sends # EOI sequence) Online Time sync : N #Send time sync message when first online Online General Int : N #Send general interrogation #Req init requests when EOI (end of initialization) received from slave EOI Time sync : Y #Send time sync message when first online EOI General Int : Y #Send general interrogation # Database definition for this session/sector # Types are as follows: # # Monitored ASDU Types # 1 = Time-tagged message (bit addressed with 2 bits/point) # 2 = Time-tagged message with relative time (bit addressed with 2 bits/point) # 3 = Measurands I (4 word values using word address using double-word address) # 4 = Time-tagged measurands with relative time (1 float value) # 5 = Identification (12 characters using a byte address) # 9 = Measurands II (9 word values using word address) #205= Siemens Meter Data (Private Range) # # Point Index = Database address in module # ASDU Index Description # 1 Bit address with each point occupying 2 bits # 2 Bit address with each point occupying 2 bits # 3 Word address with each point occupying 4 words # 4 Double-word address for the single float value # 5 Byte address with each point occupying 12 bytes # 9 Word address with each point occupying 9 words # 205 Double-word address for each meter point # # Function Code Values # Code Definition # 128 Distance protection # 160 Overcurrent protection # 176 Transformer differential protection # 192 Line Differential protection # 255 Global function type # # Database Point is the information object address in the slave unit. # # ASDU Point Function Database # Type Index Code Point START END [IEC-103 Master Session 8 Sector 2] Common ASDU Address : 7 #Range 0 to 255 Sector address #Req init requests when session first online (not req if slave sends # EOI sequence) Online Time sync : Y #Send time sync message when first online Online General Int : Y #Send general interrogation #Req init requests when EOI (end of initialization) received from slave EOI Time sync : Y #Send time sync message when first online EOI General Int : Y #Send general interrogation # Database definition for this session/sector # Types are as follows: # # Monitored ASDU Types # 1 = Time-tagged message (bit addressed with 2 bits/point) # 2 = Time-tagged message with relative time (bit addressed with 2 bits/point) # 3 = Measurands I (4 word values using word address using double-word address) # 4 = Time-tagged measurands with relative time (1 float value) # 5 = Identification (12 characters using a byte address) # 9 = Measurands II (9 word values using word address) #205= Siemens Meter Data (Private Range) # # Point Index = Database address in module # ASDU Index Description # 1 Bit address with each point occupying 2 bits # 2 Bit address with each point occupying 2 bits # 3 Word address with each point occupying 4 words # 4 Double-word address for the single float value # 5 Byte address with each point occupying 12 bytes # 9 Word address with each point occupying 9 words # 205 Double-word address for each meter point # # Function Code Values # Code Definition # 128 Distance protection # 160 Overcurrent protection # 176 Transformer differential protection # 192 Line Differential protection # 255 Global function type # # Database Point is the information object address in the slave unit. # # ASDU Point Function Database # Type Index Code Point START END # This section is used to define session 9 which runs on Port 0 [IEC-103 Master Session 9] Communication Port : 0 #Index of COM port for session (0) Sector Count : 3 #1 to 5 sectors for this slave Data Link Address : 10 #Range is 0 to 65535 DL address of slave # This section defined if Unbalanced mode utilized Failure Delay : 10 #Min Sec to delay before poll of offline slave #(0 to 2000) (Unbalanced only) Confirm Timeout : 1000 #0 to 2^32-1 mSec to wait for DL confirm Retry Count : 2 #0 to 255 retries for if no confirm #Parameters used for unbalanced mode of operation C1/C2 Poll Count Pend : 10 #class 1 or 2 polls before next slave tried (0-65535) Class 1 Polls : 5 #Max class 1 polls to this session Class 1 Pend delay : 0 #Min mSec delay between call (0 to 2^32-1) Class 2 Pend delay : 0 #Min mSec delay between call (0 to 2^32-1) Class 1 Poll delay : 0 #Min mSec delay between call (0 to 2^32-1) Class 2 Poll delay : 200 #Min mSec delay between call (0 to 2^32-1) Auto Clock Req Mode : 0 #0=Sync Only, 1=Load delay/sync, #2=Aquire delay/load delay/sync Propagation Delay : 0 #Fixed time delay for clock sync (0-65535) Response Timeout : 1000 #Timeout for confirm of req (0 to 2^32-1) ACTTERM with setpoint : Y #Y=ACTTERM last response from setpoint cmd #N=ACTCON last response from setpoint cmd [IEC-103 Master Session 9 Sector 0] Common ASDU Address : 5 #Range 0 to 255 Sector address #Req init requests when session first online (not req if slave sends # EOI sequence) Online Time sync : N #Send time sync message when first online Online General Int : N #Send general interrogation #Req init requests when EOI (end of initialization) received from slave EOI Time sync : Y #Send time sync message when first online EOI General Int : Y #Send general interrogation # Database definition for this session/sector # Types are as follows: # # Monitored ASDU Types # 1 = Time-tagged message (bit addressed with 2 bits/point) # 2 = Time-tagged message with relative time (bit addressed with 2 bits/point) # 3 = Measurands I (4 word values using word address using double-word address) # 4 = Time-tagged measurands with relative time (1 float value) # 5 = Identification (12 characters using a byte address) # 9 = Measurands II (9 word values using word address) #205= Siemens Meter Data (Private Range) # # Point Index = Database address in module # ASDU Index Description # 1 Bit address with each point occupying 2 bits # 2 Bit address with each point occupying 2 bits # 3 Word address with each point occupying 4 words # 4 Double-word address for the single float value # 5 Byte address with each point occupying 12 bytes # 9 Word address with each point occupying 9 words # 205 Double-word address for each meter point # # Function Code Values # Code Definition # 128 Distance protection # 160 Overcurrent protection # 176 Transformer differential protection # 192 Line Differential protection # 255 Global function type # # Database Point is the information object address in the slave unit. # # ASDU Point Function Database # Type Index Code Point START END [IEC-103 Master Session 9 Sector 1] Common ASDU Address : 6 #Range 0 to 255 Sector address #Req init requests when session first online (not req if slave sends # EOI sequence) Online Time sync : N #Send time sync message when first online Online General Int : N #Send general interrogation #Req init requests when EOI (end of initialization) received from slave EOI Time sync : Y #Send time sync message when first online EOI General Int : Y #Send general interrogation # Database definition for this session/sector # Types are as follows: # # Monitored ASDU Types # 1 = Time-tagged message (bit addressed with 2 bits/point) # 2 = Time-tagged message with relative time (bit addressed with 2 bits/point) # 3 = Measurands I (4 word values using word address using double-word address) # 4 = Time-tagged measurands with relative time (1 float value) # 5 = Identification (12 characters using a byte address) # 9 = Measurands II (9 word values using word address) #205= Siemens Meter Data (Private Range) # # Point Index = Database address in module # ASDU Index Description # 1 Bit address with each point occupying 2 bits # 2 Bit address with each point occupying 2 bits # 3 Word address with each point occupying 4 words # 4 Double-word address for the single float value # 5 Byte address with each point occupying 12 bytes # 9 Word address with each point occupying 9 words # 205 Double-word address for each meter point # # Function Code Values # Code Definition # 128 Distance protection # 160 Overcurrent protection # 176 Transformer differential protection # 192 Line Differential protection # 255 Global function type # # Database Point is the information object address in the slave unit. # # ASDU Point Function Database # Type Index Code Point START END [IEC-103 Master Session 9 Sector 2] Common ASDU Address : 7 #Range 0 to 255 Sector address #Req init requests when session first online (not req if slave sends # EOI sequence) Online Time sync : Y #Send time sync message when first online Online General Int : Y #Send general interrogation #Req init requests when EOI (end of initialization) received from slave EOI Time sync : Y #Send time sync message when first online EOI General Int : Y #Send general interrogation # Database definition for this session/sector # Types are as follows: # # Monitored ASDU Types # 1 = Time-tagged message (bit addressed with 2 bits/point) # 2 = Time-tagged message with relative time (bit addressed with 2 bits/point) # 3 = Measurands I (4 word values using word address using double-word address) # 4 = Time-tagged measurands with relative time (1 float value) # 5 = Identification (12 characters using a byte address) # 9 = Measurands II (9 word values using word address) #205= Siemens Meter Data (Private Range) # # Point Index = Database address in module # ASDU Index Description # 1 Bit address with each point occupying 2 bits # 2 Bit address with each point occupying 2 bits # 3 Word address with each point occupying 4 words # 4 Double-word address for the single float value # 5 Byte address with each point occupying 12 bytes # 9 Word address with each point occupying 9 words # 205 Double-word address for each meter point # # Function Code Values # Code Definition # 128 Distance protection # 160 Overcurrent protection # 176 Transformer differential protection # 192 Line Differential protection # 255 Global function type # # Database Point is the information object address in the slave unit. # # ASDU Point Function Database # Type Index Code Point START END # This section is used to define session 10 which runs on Port 0 [IEC-103 Master Session 10] Communication Port : 0 #Index of COM port for session (0) Sector Count : 3 #1 to 5 sectors for this slave Data Link Address : 11 #Range is 0 to 65535 DL address of slave # This section defined if Unbalanced mode utilized Failure Delay : 10 #Min Sec to delay before poll of offline slave #(0 to 2000) (Unbalanced only) Confirm Timeout : 1000 #0 to 2^32-1 mSec to wait for DL confirm Retry Count : 2 #0 to 255 retries for if no confirm #Parameters used for unbalanced mode of operation C1/C2 Poll Count Pend : 10 #class 1 or 2 polls before next slave tried (0-65535) Class 1 Polls : 5 #Max class 1 polls to this session Class 1 Pend delay : 0 #Min mSec delay between call (0 to 2^32-1) Class 2 Pend delay : 0 #Min mSec delay between call (0 to 2^32-1) Class 1 Poll delay : 0 #Min mSec delay between call (0 to 2^32-1) Class 2 Poll delay : 200 #Min mSec delay between call (0 to 2^32-1) Auto Clock Req Mode : 0 #0=Sync Only, 1=Load delay/sync, #2=Aquire delay/load delay/sync Propagation Delay : 0 #Fixed time delay for clock sync (0-65535) Response Timeout : 1000 #Timeout for confirm of req (0 to 2^32-1) ACTTERM with setpoint : Y #Y=ACTTERM last response from setpoint cmd #N=ACTCON last response from setpoint cmd [IEC-103 Master Session 10 Sector 0] Common ASDU Address : 5 #Range 0 to 255 Sector address #Req init requests when session first online (not req if slave sends # EOI sequence) Online Time sync : N #Send time sync message when first online Online General Int : N #Send general interrogation #Req init requests when EOI (end of initialization) received from slave EOI Time sync : Y #Send time sync message when first online EOI General Int : Y #Send general interrogation # Database definition for this session/sector # Types are as follows: # # Monitored ASDU Types # 1 = Time-tagged message (bit addressed with 2 bits/point) # 2 = Time-tagged message with relative time (bit addressed with 2 bits/point) # 3 = Measurands I (4 word values using word address using double-word address) # 4 = Time-tagged measurands with relative time (1 float value) # 5 = Identification (12 characters using a byte address) # 9 = Measurands II (9 word values using word address) #205= Siemens Meter Data (Private Range) # # Point Index = Database address in module # ASDU Index Description # 1 Bit address with each point occupying 2 bits # 2 Bit address with each point occupying 2 bits # 3 Word address with each point occupying 4 words # 4 Double-word address for the single float value # 5 Byte address with each point occupying 12 bytes # 9 Word address with each point occupying 9 words # 205 Double-word address for each meter point # # Function Code Values # Code Definition # 128 Distance protection # 160 Overcurrent protection # 176 Transformer differential protection # 192 Line Differential protection # 255 Global function type # # Database Point is the information object address in the slave unit. # # ASDU Point Function Database # Type Index Code Point START END [IEC-103 Master Session 10 Sector 1] Common ASDU Address : 6 #Range 0 to 255 Sector address #Req init requests when session first online (not req if slave sends # EOI sequence) Online Time sync : N #Send time sync message when first online Online General Int : N #Send general interrogation #Req init requests when EOI (end of initialization) received from slave EOI Time sync : Y #Send time sync message when first online EOI General Int : Y #Send general interrogation # Database definition for this session/sector # Types are as follows: # # Monitored ASDU Types # 1 = Time-tagged message (bit addressed with 2 bits/point) # 2 = Time-tagged message with relative time (bit addressed with 2 bits/point) # 3 = Measurands I (4 word values using word address using double-word address) # 4 = Time-tagged measurands with relative time (1 float value) # 5 = Identification (12 characters using a byte address) # 9 = Measurands II (9 word values using word address) #205= Siemens Meter Data (Private Range) # # Point Index = Database address in module # ASDU Index Description # 1 Bit address with each point occupying 2 bits # 2 Bit address with each point occupying 2 bits # 3 Word address with each point occupying 4 words # 4 Double-word address for the single float value # 5 Byte address with each point occupying 12 bytes # 9 Word address with each point occupying 9 words # 205 Double-word address for each meter point # # Function Code Values # Code Definition # 128 Distance protection # 160 Overcurrent protection # 176 Transformer differential protection # 192 Line Differential protection # 255 Global function type # # Database Point is the information object address in the slave unit. # # ASDU Point Function Database # Type Index Code Point START END [IEC-103 Master Session 10 Sector 2] Common ASDU Address : 7 #Range 0 to 255 Sector address #Req init requests when session first online (not req if slave sends # EOI sequence) Online Time sync : Y #Send time sync message when first online Online General Int : Y #Send general interrogation #Req init requests when EOI (end of initialization) received from slave EOI Time sync : Y #Send time sync message when first online EOI General Int : Y #Send general interrogation # Database definition for this session/sector # Types are as follows: # # Monitored ASDU Types # 1 = Time-tagged message (bit addressed with 2 bits/point) # 2 = Time-tagged message with relative time (bit addressed with 2 bits/point) # 3 = Measurands I (4 word values using word address using double-word address) # 4 = Time-tagged measurands with relative time (1 float value) # 5 = Identification (12 characters using a byte address) # 9 = Measurands II (9 word values using word address) #205= Siemens Meter Data (Private Range) # # Point Index = Database address in module # ASDU Index Description # 1 Bit address with each point occupying 2 bits # 2 Bit address with each point occupying 2 bits # 3 Word address with each point occupying 4 words # 4 Double-word address for the single float value # 5 Byte address with each point occupying 12 bytes # 9 Word address with each point occupying 9 words # 205 Double-word address for each meter point # # Function Code Values # Code Definition # 128 Distance protection # 160 Overcurrent protection # 176 Transformer differential protection # 192 Line Differential protection # 255 Global function type # # Database Point is the information object address in the slave unit. # # ASDU Point Function Database # Type Index Code Point START END # This section is used to define session 11 which runs on Port 0 [IEC-103 Master Session 11] Communication Port : 0 #Index of COM port for session (0) Sector Count : 3 #1 to 5 sectors for this slave Data Link Address : 12 #Range is 0 to 65535 DL address of slave # This section defined if Unbalanced mode utilized Failure Delay : 10 #Min Sec to delay before poll of offline slave #(0 to 2000) (Unbalanced only) Confirm Timeout : 1000 #0 to 2^32-1 mSec to wait for DL confirm Retry Count : 2 #0 to 255 retries for if no confirm #Parameters used for unbalanced mode of operation C1/C2 Poll Count Pend : 10 #class 1 or 2 polls before next slave tried (0-65535) Class 1 Polls : 5 #Max class 1 polls to this session Class 1 Pend delay : 0 #Min mSec delay between call (0 to 2^32-1) Class 2 Pend delay : 0 #Min mSec delay between call (0 to 2^32-1) Class 1 Poll delay : 0 #Min mSec delay between call (0 to 2^32-1) Class 2 Poll delay : 200 #Min mSec delay between call (0 to 2^32-1) Auto Clock Req Mode : 0 #0=Sync Only, 1=Load delay/sync, #2=Aquire delay/load delay/sync Propagation Delay : 0 #Fixed time delay for clock sync (0-65535) Response Timeout : 1000 #Timeout for confirm of req (0 to 2^32-1) ACTTERM with setpoint : Y #Y=ACTTERM last response from setpoint cmd #N=ACTCON last response from setpoint cmd [IEC-103 Master Session 11 Sector 0] Common ASDU Address : 5 #Range 0 to 255 Sector address #Req init requests when session first online (not req if slave sends # EOI sequence) Online Time sync : N #Send time sync message when first online Online General Int : N #Send general interrogation #Req init requests when EOI (end of initialization) received from slave EOI Time sync : Y #Send time sync message when first online EOI General Int : Y #Send general interrogation # Database definition for this session/sector # Types are as follows: # # Monitored ASDU Types # 1 = Time-tagged message (bit addressed with 2 bits/point) # 2 = Time-tagged message with relative time (bit addressed with 2 bits/point) # 3 = Measurands I (4 word values using word address using double-word address) # 4 = Time-tagged measurands with relative time (1 float value) # 5 = Identification (12 characters using a byte address) # 9 = Measurands II (9 word values using word address) #205= Siemens Meter Data (Private Range) # # Point Index = Database address in module # ASDU Index Description # 1 Bit address with each point occupying 2 bits # 2 Bit address with each point occupying 2 bits # 3 Word address with each point occupying 4 words # 4 Double-word address for the single float value # 5 Byte address with each point occupying 12 bytes # 9 Word address with each point occupying 9 words # 205 Double-word address for each meter point # # Function Code Values # Code Definition # 128 Distance protection # 160 Overcurrent protection # 176 Transformer differential protection # 192 Line Differential protection # 255 Global function type # # Database Point is the information object address in the slave unit. # # ASDU Point Function Database # Type Index Code Point START END [IEC-103 Master Session 11 Sector 1] Common ASDU Address : 6 #Range 0 to 255 Sector address #Req init requests when session first online (not req if slave sends # EOI sequence) Online Time sync : N #Send time sync message when first online Online General Int : N #Send general interrogation #Req init requests when EOI (end of initialization) received from slave EOI Time sync : Y #Send time sync message when first online EOI General Int : Y #Send general interrogation # Database definition for this session/sector # Types are as follows: # # Monitored ASDU Types # 1 = Time-tagged message (bit addressed with 2 bits/point) # 2 = Time-tagged message with relative time (bit addressed with 2 bits/point) # 3 = Measurands I (4 word values using word address using double-word address) # 4 = Time-tagged measurands with relative time (1 float value) # 5 = Identification (12 characters using a byte address) # 9 = Measurands II (9 word values using word address) #205= Siemens Meter Data (Private Range) # # Point Index = Database address in module # ASDU Index Description # 1 Bit address with each point occupying 2 bits # 2 Bit address with each point occupying 2 bits # 3 Word address with each point occupying 4 words # 4 Double-word address for the single float value # 5 Byte address with each point occupying 12 bytes # 9 Word address with each point occupying 9 words # 205 Double-word address for each meter point # # Function Code Values # Code Definition # 128 Distance protection # 160 Overcurrent protection # 176 Transformer differential protection # 192 Line Differential protection # 255 Global function type # # Database Point is the information object address in the slave unit. # # ASDU Point Function Database # Type Index Code Point START END [IEC-103 Master Session 11 Sector 2] Common ASDU Address : 7 #Range 0 to 255 Sector address #Req init requests when session first online (not req if slave sends # EOI sequence) Online Time sync : Y #Send time sync message when first online Online General Int : Y #Send general interrogation #Req init requests when EOI (end of initialization) received from slave EOI Time sync : Y #Send time sync message when first online EOI General Int : Y #Send general interrogation # Database definition for this session/sector # Types are as follows: # # Monitored ASDU Types # 1 = Time-tagged message (bit addressed with 2 bits/point) # 2 = Time-tagged message with relative time (bit addressed with 2 bits/point) # 3 = Measurands I (4 word values using word address using double-word address) # 4 = Time-tagged measurands with relative time (1 float value) # 5 = Identification (12 characters using a byte address) # 9 = Measurands II (9 word values using word address) #205= Siemens Meter Data (Private Range) # # Point Index = Database address in module # ASDU Index Description # 1 Bit address with each point occupying 2 bits # 2 Bit address with each point occupying 2 bits # 3 Word address with each point occupying 4 words # 4 Double-word address for the single float value # 5 Byte address with each point occupying 12 bytes # 9 Word address with each point occupying 9 words # 205 Double-word address for each meter point # # Function Code Values # Code Definition # 128 Distance protection # 160 Overcurrent protection # 176 Transformer differential protection # 192 Line Differential protection # 255 Global function type # # Database Point is the information object address in the slave unit. # # ASDU Point Function Database # Type Index Code Point START END # This section is used to define session 12 which runs on Port 0 [IEC-103 Master Session 12] Communication Port : 0 #Index of COM port for session (0) Sector Count : 3 #1 to 5 sectors for this slave Data Link Address : 13 #Range is 0 to 65535 DL address of slave # This section defined if Unbalanced mode utilized Failure Delay : 10 #Min Sec to delay before poll of offline slave #(0 to 2000) (Unbalanced only) Confirm Timeout : 1000 #0 to 2^32-1 mSec to wait for DL confirm Retry Count : 2 #0 to 255 retries for if no confirm #Parameters used for unbalanced mode of operation C1/C2 Poll Count Pend : 10 #class 1 or 2 polls before next slave tried (0-65535) Class 1 Polls : 5 #Max class 1 polls to this session Class 1 Pend delay : 0 #Min mSec delay between call (0 to 2^32-1) Class 2 Pend delay : 0 #Min mSec delay between call (0 to 2^32-1) Class 1 Poll delay : 0 #Min mSec delay between call (0 to 2^32-1) Class 2 Poll delay : 200 #Min mSec delay between call (0 to 2^32-1) Auto Clock Req Mode : 0 #0=Sync Only, 1=Load delay/sync, #2=Aquire delay/load delay/sync Propagation Delay : 0 #Fixed time delay for clock sync (0-65535) Response Timeout : 1000 #Timeout for confirm of req (0 to 2^32-1) ACTTERM with setpoint : Y #Y=ACTTERM last response from setpoint cmd #N=ACTCON last response from setpoint cmd [IEC-103 Master Session 12 Sector 0] Common ASDU Address : 5 #Range 0 to 255 Sector address #Req init requests when session first online (not req if slave sends # EOI sequence) Online Time sync : N #Send time sync message when first online Online General Int : N #Send general interrogation #Req init requests when EOI (end of initialization) received from slave EOI Time sync : Y #Send time sync message when first online EOI General Int : Y #Send general interrogation # Database definition for this session/sector # Types are as follows: # # Monitored ASDU Types # 1 = Time-tagged message (bit addressed with 2 bits/point) # 2 = Time-tagged message with relative time (bit addressed with 2 bits/point) # 3 = Measurands I (4 word values using word address using double-word address) # 4 = Time-tagged measurands with relative time (1 float value) # 5 = Identification (12 characters using a byte address) # 9 = Measurands II (9 word values using word address) #205= Siemens Meter Data (Private Range) # # Point Index = Database address in module # ASDU Index Description # 1 Bit address with each point occupying 2 bits # 2 Bit address with each point occupying 2 bits # 3 Word address with each point occupying 4 words # 4 Double-word address for the single float value # 5 Byte address with each point occupying 12 bytes # 9 Word address with each point occupying 9 words # 205 Double-word address for each meter point # # Function Code Values # Code Definition # 128 Distance protection # 160 Overcurrent protection # 176 Transformer differential protection # 192 Line Differential protection # 255 Global function type # # Database Point is the information object address in the slave unit. # # ASDU Point Function Database # Type Index Code Point START END [IEC-103 Master Session 12 Sector 1] Common ASDU Address : 6 #Range 0 to 255 Sector address #Req init requests when session first online (not req if slave sends # EOI sequence) Online Time sync : N #Send time sync message when first online Online General Int : N #Send general interrogation #Req init requests when EOI (end of initialization) received from slave EOI Time sync : Y #Send time sync message when first online EOI General Int : Y #Send general interrogation # Database definition for this session/sector # Types are as follows: # # Monitored ASDU Types # 1 = Time-tagged message (bit addressed with 2 bits/point) # 2 = Time-tagged message with relative time (bit addressed with 2 bits/point) # 3 = Measurands I (4 word values using word address using double-word address) # 4 = Time-tagged measurands with relative time (1 float value) # 5 = Identification (12 characters using a byte address) # 9 = Measurands II (9 word values using word address) #205= Siemens Meter Data (Private Range) # # Point Index = Database address in module # ASDU Index Description # 1 Bit address with each point occupying 2 bits # 2 Bit address with each point occupying 2 bits # 3 Word address with each point occupying 4 words # 4 Double-word address for the single float value # 5 Byte address with each point occupying 12 bytes # 9 Word address with each point occupying 9 words # 205 Double-word address for each meter point # # Function Code Values # Code Definition # 128 Distance protection # 160 Overcurrent protection # 176 Transformer differential protection # 192 Line Differential protection # 255 Global function type # # Database Point is the information object address in the slave unit. # # ASDU Point Function Database # Type Index Code Point START END [IEC-103 Master Session 12 Sector 2] Common ASDU Address : 7 #Range 0 to 255 Sector address #Req init requests when session first online (not req if slave sends # EOI sequence) Online Time sync : Y #Send time sync message when first online Online General Int : Y #Send general interrogation #Req init requests when EOI (end of initialization) received from slave EOI Time sync : Y #Send time sync message when first online EOI General Int : Y #Send general interrogation # Database definition for this session/sector # Types are as follows: # # Monitored ASDU Types # 1 = Time-tagged message (bit addressed with 2 bits/point) # 2 = Time-tagged message with relative time (bit addressed with 2 bits/point) # 3 = Measurands I (4 word values using word address using double-word address) # 4 = Time-tagged measurands with relative time (1 float value) # 5 = Identification (12 characters using a byte address) # 9 = Measurands II (9 word values using word address) #205= Siemens Meter Data (Private Range) # # Point Index = Database address in module # ASDU Index Description # 1 Bit address with each point occupying 2 bits # 2 Bit address with each point occupying 2 bits # 3 Word address with each point occupying 4 words # 4 Double-word address for the single float value # 5 Byte address with each point occupying 12 bytes # 9 Word address with each point occupying 9 words # 205 Double-word address for each meter point # # Function Code Values # Code Definition # 128 Distance protection # 160 Overcurrent protection # 176 Transformer differential protection # 192 Line Differential protection # 255 Global function type # # Database Point is the information object address in the slave unit. # # ASDU Point Function Database # Type Index Code Point START END # This section is used to define session 13 which runs on Port 0 [IEC-103 Master Session 13] Communication Port : 0 #Index of COM port for session (0) Sector Count : 3 #1 to 5 sectors for this slave Data Link Address : 14 #Range is 0 to 65535 DL address of slave # This section defined if Unbalanced mode utilized Failure Delay : 10 #Min Sec to delay before poll of offline slave #(0 to 2000) (Unbalanced only) Confirm Timeout : 1000 #0 to 2^32-1 mSec to wait for DL confirm Retry Count : 2 #0 to 255 retries for if no confirm #Parameters used for unbalanced mode of operation C1/C2 Poll Count Pend : 10 #class 1 or 2 polls before next slave tried (0-65535) Class 1 Polls : 5 #Max class 1 polls to this session Class 1 Pend delay : 0 #Min mSec delay between call (0 to 2^32-1) Class 2 Pend delay : 0 #Min mSec delay between call (0 to 2^32-1) Class 1 Poll delay : 0 #Min mSec delay between call (0 to 2^32-1) Class 2 Poll delay : 200 #Min mSec delay between call (0 to 2^32-1) Auto Clock Req Mode : 0 #0=Sync Only, 1=Load delay/sync, #2=Aquire delay/load delay/sync Propagation Delay : 0 #Fixed time delay for clock sync (0-65535) Response Timeout : 1000 #Timeout for confirm of req (0 to 2^32-1) ACTTERM with setpoint : Y #Y=ACTTERM last response from setpoint cmd #N=ACTCON last response from setpoint cmd [IEC-103 Master Session 13 Sector 0] Common ASDU Address : 5 #Range 0 to 255 Sector address #Req init requests when session first online (not req if slave sends # EOI sequence) Online Time sync : N #Send time sync message when first online Online General Int : N #Send general interrogation #Req init requests when EOI (end of initialization) received from slave EOI Time sync : Y #Send time sync message when first online EOI General Int : Y #Send general interrogation # Database definition for this session/sector # Types are as follows: # # Monitored ASDU Types # 1 = Time-tagged message (bit addressed with 2 bits/point) # 2 = Time-tagged message with relative time (bit addressed with 2 bits/point) # 3 = Measurands I (4 word values using word address using double-word address) # 4 = Time-tagged measurands with relative time (1 float value) # 5 = Identification (12 characters using a byte address) # 9 = Measurands II (9 word values using word address) #205= Siemens Meter Data (Private Range) # # Point Index = Database address in module # ASDU Index Description # 1 Bit address with each point occupying 2 bits # 2 Bit address with each point occupying 2 bits # 3 Word address with each point occupying 4 words # 4 Double-word address for the single float value # 5 Byte address with each point occupying 12 bytes # 9 Word address with each point occupying 9 words # 205 Double-word address for each meter point # # Function Code Values # Code Definition # 128 Distance protection # 160 Overcurrent protection # 176 Transformer differential protection # 192 Line Differential protection # 255 Global function type # # Database Point is the information object address in the slave unit. # # ASDU Point Function Database # Type Index Code Point START END [IEC-103 Master Session 13 Sector 1] Common ASDU Address : 6 #Range 0 to 255 Sector address #Req init requests when session first online (not req if slave sends # EOI sequence) Online Time sync : N #Send time sync message when first online Online General Int : N #Send general interrogation #Req init requests when EOI (end of initialization) received from slave EOI Time sync : Y #Send time sync message when first online EOI General Int : Y #Send general interrogation # Database definition for this session/sector # Types are as follows: # # Monitored ASDU Types # 1 = Time-tagged message (bit addressed with 2 bits/point) # 2 = Time-tagged message with relative time (bit addressed with 2 bits/point) # 3 = Measurands I (4 word values using word address using double-word address) # 4 = Time-tagged measurands with relative time (1 float value) # 5 = Identification (12 characters using a byte address) # 9 = Measurands II (9 word values using word address) #205= Siemens Meter Data (Private Range) # # Point Index = Database address in module # ASDU Index Description # 1 Bit address with each point occupying 2 bits # 2 Bit address with each point occupying 2 bits # 3 Word address with each point occupying 4 words # 4 Double-word address for the single float value # 5 Byte address with each point occupying 12 bytes # 9 Word address with each point occupying 9 words # 205 Double-word address for each meter point # # Function Code Values # Code Definition # 128 Distance protection # 160 Overcurrent protection # 176 Transformer differential protection # 192 Line Differential protection # 255 Global function type # # Database Point is the information object address in the slave unit. # # ASDU Point Function Database # Type Index Code Point START END [IEC-103 Master Session 13 Sector 2] Common ASDU Address : 7 #Range 0 to 255 Sector address #Req init requests when session first online (not req if slave sends # EOI sequence) Online Time sync : Y #Send time sync message when first online Online General Int : Y #Send general interrogation #Req init requests when EOI (end of initialization) received from slave EOI Time sync : Y #Send time sync message when first online EOI General Int : Y #Send general interrogation # Database definition for this session/sector # Types are as follows: # # Monitored ASDU Types # 1 = Time-tagged message (bit addressed with 2 bits/point) # 2 = Time-tagged message with relative time (bit addressed with 2 bits/point) # 3 = Measurands I (4 word values using word address using double-word address) # 4 = Time-tagged measurands with relative time (1 float value) # 5 = Identification (12 characters using a byte address) # 9 = Measurands II (9 word values using word address) #205= Siemens Meter Data (Private Range) # # Point Index = Database address in module # ASDU Index Description # 1 Bit address with each point occupying 2 bits # 2 Bit address with each point occupying 2 bits # 3 Word address with each point occupying 4 words # 4 Double-word address for the single float value # 5 Byte address with each point occupying 12 bytes # 9 Word address with each point occupying 9 words # 205 Double-word address for each meter point # # Function Code Values # Code Definition # 128 Distance protection # 160 Overcurrent protection # 176 Transformer differential protection # 192 Line Differential protection # 255 Global function type # # Database Point is the information object address in the slave unit. # # ASDU Point Function Database # Type Index Code Point START END # This section is used to define session 14 which runs on Port 0 [IEC-103 Master Session 14] Communication Port : 0 #Index of COM port for session (0) Sector Count : 3 #1 to 5 sectors for this slave Data Link Address : 15 #Range is 0 to 65535 DL address of slave # This section defined if Unbalanced mode utilized Failure Delay : 10 #Min Sec to delay before poll of offline slave #(0 to 2000) (Unbalanced only) Confirm Timeout : 1000 #0 to 2^32-1 mSec to wait for DL confirm Retry Count : 2 #0 to 255 retries for if no confirm #Parameters used for unbalanced mode of operation C1/C2 Poll Count Pend : 10 #class 1 or 2 polls before next slave tried (0-65535) Class 1 Polls : 5 #Max class 1 polls to this session Class 1 Pend delay : 0 #Min mSec delay between call (0 to 2^32-1) Class 2 Pend delay : 0 #Min mSec delay between call (0 to 2^32-1) Class 1 Poll delay : 0 #Min mSec delay between call (0 to 2^32-1) Class 2 Poll delay : 200 #Min mSec delay between call (0 to 2^32-1) Auto Clock Req Mode : 0 #0=Sync Only, 1=Load delay/sync, #2=Aquire delay/load delay/sync Propagation Delay : 0 #Fixed time delay for clock sync (0-65535) Response Timeout : 1000 #Timeout for confirm of req (0 to 2^32-1) ACTTERM with setpoint : Y #Y=ACTTERM last response from setpoint cmd #N=ACTCON last response from setpoint cmd [IEC-103 Master Session 14 Sector 0] Common ASDU Address : 5 #Range 0 to 255 Sector address #Req init requests when session first online (not req if slave sends # EOI sequence) Online Time sync : N #Send time sync message when first online Online General Int : N #Send general interrogation #Req init requests when EOI (end of initialization) received from slave EOI Time sync : Y #Send time sync message when first online EOI General Int : Y #Send general interrogation # Database definition for this session/sector # Types are as follows: # # Monitored ASDU Types # 1 = Time-tagged message (bit addressed with 2 bits/point) # 2 = Time-tagged message with relative time (bit addressed with 2 bits/point) # 3 = Measurands I (4 word values using word address using double-word address) # 4 = Time-tagged measurands with relative time (1 float value) # 5 = Identification (12 characters using a byte address) # 9 = Measurands II (9 word values using word address) #205= Siemens Meter Data (Private Range) # # Point Index = Database address in module # ASDU Index Description # 1 Bit address with each point occupying 2 bits # 2 Bit address with each point occupying 2 bits # 3 Word address with each point occupying 4 words # 4 Double-word address for the single float value # 5 Byte address with each point occupying 12 bytes # 9 Word address with each point occupying 9 words # 205 Double-word address for each meter point # # Function Code Values # Code Definition # 128 Distance protection # 160 Overcurrent protection # 176 Transformer differential protection # 192 Line Differential protection # 255 Global function type # # Database Point is the information object address in the slave unit. # # ASDU Point Function Database # Type Index Code Point START END [IEC-103 Master Session 14 Sector 1] Common ASDU Address : 6 #Range 0 to 255 Sector address #Req init requests when session first online (not req if slave sends # EOI sequence) Online Time sync : N #Send time sync message when first online Online General Int : N #Send general interrogation #Req init requests when EOI (end of initialization) received from slave EOI Time sync : Y #Send time sync message when first online EOI General Int : Y #Send general interrogation # Database definition for this session/sector # Types are as follows: # # Monitored ASDU Types # 1 = Time-tagged message (bit addressed with 2 bits/point) # 2 = Time-tagged message with relative time (bit addressed with 2 bits/point) # 3 = Measurands I (4 word values using word address using double-word address) # 4 = Time-tagged measurands with relative time (1 float value) # 5 = Identification (12 characters using a byte address) # 9 = Measurands II (9 word values using word address) #205= Siemens Meter Data (Private Range) # # Point Index = Database address in module # ASDU Index Description # 1 Bit address with each point occupying 2 bits # 2 Bit address with each point occupying 2 bits # 3 Word address with each point occupying 4 words # 4 Double-word address for the single float value # 5 Byte address with each point occupying 12 bytes # 9 Word address with each point occupying 9 words # 205 Double-word address for each meter point # # Function Code Values # Code Definition # 128 Distance protection # 160 Overcurrent protection # 176 Transformer differential protection # 192 Line Differential protection # 255 Global function type # # Database Point is the information object address in the slave unit. # # ASDU Point Function Database # Type Index Code Point START END [IEC-103 Master Session 14 Sector 2] Common ASDU Address : 7 #Range 0 to 255 Sector address #Req init requests when session first online (not req if slave sends # EOI sequence) Online Time sync : Y #Send time sync message when first online Online General Int : Y #Send general interrogation #Req init requests when EOI (end of initialization) received from slave EOI Time sync : Y #Send time sync message when first online EOI General Int : Y #Send general interrogation # Database definition for this session/sector # Types are as follows: # # Monitored ASDU Types # 1 = Time-tagged message (bit addressed with 2 bits/point) # 2 = Time-tagged message with relative time (bit addressed with 2 bits/point) # 3 = Measurands I (4 word values using word address using double-word address) # 4 = Time-tagged measurands with relative time (1 float value) # 5 = Identification (12 characters using a byte address) # 9 = Measurands II (9 word values using word address) #205= Siemens Meter Data (Private Range) # # Point Index = Database address in module # ASDU Index Description # 1 Bit address with each point occupying 2 bits # 2 Bit address with each point occupying 2 bits # 3 Word address with each point occupying 4 words # 4 Double-word address for the single float value # 5 Byte address with each point occupying 12 bytes # 9 Word address with each point occupying 9 words # 205 Double-word address for each meter point # # Function Code Values # Code Definition # 128 Distance protection # 160 Overcurrent protection # 176 Transformer differential protection # 192 Line Differential protection # 255 Global function type # # Database Point is the information object address in the slave unit. # # ASDU Point Function Database # Type Index Code Point START END # This section is used to define session 15 which runs on Port 0 [IEC-103 Master Session 15] Communication Port : 0 #Index of COM port for session (0) Sector Count : 3 #1 to 5 sectors for this slave Data Link Address : 16 #Range is 0 to 65535 DL address of slave # This section defined if Unbalanced mode utilized Failure Delay : 10 #Min Sec to delay before poll of offline slave #(0 to 2000) (Unbalanced only) Confirm Timeout : 1000 #0 to 2^32-1 mSec to wait for DL confirm Retry Count : 2 #0 to 255 retries for if no confirm #Parameters used for unbalanced mode of operation C1/C2 Poll Count Pend : 10 #class 1 or 2 polls before next slave tried (0-65535) Class 1 Polls : 5 #Max class 1 polls to this session Class 1 Pend delay : 0 #Min mSec delay between call (0 to 2^32-1) Class 2 Pend delay : 0 #Min mSec delay between call (0 to 2^32-1) Class 1 Poll delay : 0 #Min mSec delay between call (0 to 2^32-1) Class 2 Poll delay : 200 #Min mSec delay between call (0 to 2^32-1) Auto Clock Req Mode : 0 #0=Sync Only, 1=Load delay/sync, #2=Aquire delay/load delay/sync Propagation Delay : 0 #Fixed time delay for clock sync (0-65535) Response Timeout : 1000 #Timeout for confirm of req (0 to 2^32-1) ACTTERM with setpoint : Y #Y=ACTTERM last response from setpoint cmd #N=ACTCON last response from setpoint cmd [IEC-103 Master Session 15 Sector 0] Common ASDU Address : 5 #Range 0 to 255 Sector address #Req init requests when session first online (not req if slave sends # EOI sequence) Online Time sync : N #Send time sync message when first online Online General Int : N #Send general interrogation #Req init requests when EOI (end of initialization) received from slave EOI Time sync : Y #Send time sync message when first online EOI General Int : Y #Send general interrogation # Database definition for this session/sector # Types are as follows: # # Monitored ASDU Types # 1 = Time-tagged message (bit addressed with 2 bits/point) # 2 = Time-tagged message with relative time (bit addressed with 2 bits/point) # 3 = Measurands I (4 word values using word address using double-word address) # 4 = Time-tagged measurands with relative time (1 float value) # 5 = Identification (12 characters using a byte address) # 9 = Measurands II (9 word values using word address) #205= Siemens Meter Data (Private Range) # # Point Index = Database address in module # ASDU Index Description # 1 Bit address with each point occupying 2 bits # 2 Bit address with each point occupying 2 bits # 3 Word address with each point occupying 4 words # 4 Double-word address for the single float value # 5 Byte address with each point occupying 12 bytes # 9 Word address with each point occupying 9 words # 205 Double-word address for each meter point # # Function Code Values # Code Definition # 128 Distance protection # 160 Overcurrent protection # 176 Transformer differential protection # 192 Line Differential protection # 255 Global function type # # Database Point is the information object address in the slave unit. # # ASDU Point Function Database # Type Index Code Point START END [IEC-103 Master Session 15 Sector 1] Common ASDU Address : 6 #Range 0 to 255 Sector address #Req init requests when session first online (not req if slave sends # EOI sequence) Online Time sync : N #Send time sync message when first online Online General Int : N #Send general interrogation #Req init requests when EOI (end of initialization) received from slave EOI Time sync : Y #Send time sync message when first online EOI General Int : Y #Send general interrogation # Database definition for this session/sector # Types are as follows: # # Monitored ASDU Types # 1 = Time-tagged message (bit addressed with 2 bits/point) # 2 = Time-tagged message with relative time (bit addressed with 2 bits/point) # 3 = Measurands I (4 word values using word address using double-word address) # 4 = Time-tagged measurands with relative time (1 float value) # 5 = Identification (12 characters using a byte address) # 9 = Measurands II (9 word values using word address) #205= Siemens Meter Data (Private Range) # # Point Index = Database address in module # ASDU Index Description # 1 Bit address with each point occupying 2 bits # 2 Bit address with each point occupying 2 bits # 3 Word address with each point occupying 4 words # 4 Double-word address for the single float value # 5 Byte address with each point occupying 12 bytes # 9 Word address with each point occupying 9 words # 205 Double-word address for each meter point # # Function Code Values # Code Definition # 128 Distance protection # 160 Overcurrent protection # 176 Transformer differential protection # 192 Line Differential protection # 255 Global function type # # Database Point is the information object address in the slave unit. # # ASDU Point Function Database # Type Index Code Point START END [IEC-103 Master Session 15 Sector 2] Common ASDU Address : 7 #Range 0 to 255 Sector address #Req init requests when session first online (not req if slave sends # EOI sequence) Online Time sync : Y #Send time sync message when first online Online General Int : Y #Send general interrogation #Req init requests when EOI (end of initialization) received from slave EOI Time sync : Y #Send time sync message when first online EOI General Int : Y #Send general interrogation # Database definition for this session/sector # Types are as follows: # # Monitored ASDU Types # 1 = Time-tagged message (bit addressed with 2 bits/point) # 2 = Time-tagged message with relative time (bit addressed with 2 bits/point) # 3 = Measurands I (4 word values using word address using double-word address) # 4 = Time-tagged measurands with relative time (1 float value) # 5 = Identification (12 characters using a byte address) # 9 = Measurands II (9 word values using word address) #205= Siemens Meter Data (Private Range) # # Point Index = Database address in module # ASDU Index Description # 1 Bit address with each point occupying 2 bits # 2 Bit address with each point occupying 2 bits # 3 Word address with each point occupying 4 words # 4 Double-word address for the single float value # 5 Byte address with each point occupying 12 bytes # 9 Word address with each point occupying 9 words # 205 Double-word address for each meter point # # Function Code Values # Code Definition # 128 Distance protection # 160 Overcurrent protection # 176 Transformer differential protection # 192 Line Differential protection # 255 Global function type # # Database Point is the information object address in the slave unit. # # ASDU Point Function Database # Type Index Code Point START END [IEC-103 Master Commands] # # Enable code field is as follows: # 0 = Disabled # 1 = Enabled with Poll Interval (seconds) utilized # 2 = Conditional (executed when point in database changes) # # Database Index is the location in the module's database to use as the source # for the data in the command. The data type field determines # the meaning of the index as follows: # Type Description DB Index type # ---- ----------------------------------- -------------------- # 6 Clock synchronization NA # 7 General interrogataion NA # 20 General Command Bit address # # Poll Interval field is utilized when the Enable Code is set to 1. This field # determines the minimum number of seconds to wait between each # execution of the command. # # Session Index represents the session index in the module to associate with the # command. This index is set when the session is read in from # this file. The range of values for this field is 0 to 31. # # Sector Index represents the sector index for the specific session. The range # of values for this field is 0 to 4. # # Data type file represents the ASDU type as follows: # 6 = Time synchronization # 7 = General Interrogation # 20 = General Command # # Function code # Code Definition # 128 Distance protection # 160 Overcurrent protection # 176 Transformer differential protection # 192 Line Differential protection # 255 Global function type # # Point Index field is used to specify the address in the remote slave device # of the point to interact with. # # # Enable Database Poll Session Sector Data Func Point # Code Index Interval Index Index Type Code Index START 1 100 10 0 0 6 255 0 0 100 10 1 0 6 255 0 0 100 10 1 0 6 255 0 0 100 10 1 0 6 255 0 0 100 10 1 0 6 255 0 1 100 10 0 0 7 255 0 0 100 10 1 0 7 255 0 0 100 10 1 0 7 255 0 0 100 10 1 0 7 255 0 0 100 10 1 0 7 255 0 1 100 10 0 0 20 128 0 0 100 10 1 0 20 128 0 0 100 10 1 0 20 128 0 0 100 10 1 0 20 128 0 0 100 10 1 0 20 128 0 END