PLX51-HART-8I

8 Channel HART® Input Module

PLX51-HART-8I

This product will be released soon. For more information Contact Us

The PLX51-HART-8I supports the interfacing of HART devices on each of the 8 analog HART channels with either EtherNet/IP™ (Target or Originator) or Modbus Client/Server (TCP, RTU232, RTU485) protocols. Each channel supports both voltage and current input options (e.g., 4-20mA, Voltage, etc.), with or without HART communication enabled.

The PLX51-HART-8I supports up to 8 HART devices per channel (multidrop).

图像

Click on image(s) to enlarge
Drag with the mouse. Click for close.

特性 优势

  • HART Input Channels: Supports 8 isolated HART input channels, accommodating up to 8 HART devices per channel, for a total of 64 HART devices.
  • Communication Interfaces: Operates with EtherNet/IP (target or originator) and Modbus TCP, RTU232, or RTU485 (client or server).
  • Custom HART Commands: Allows for custom acyclic HART commands to all connected HART devices.
  • Analog Input Options: Supports various analog input ranges including 0-20mA, 4-20mA, 0-10Vdc, and 0-20mA or 4-20mA with an external resistor.
  • Network Redundancy: Equipped with dual Ethernet ports for Linear or Device-Level-Ring (DLR) topology.
  • Simplified Configuration: Facilitates easier setup and configuration through auto-generated .L5X files that can be imported into the controller.

规格

HART

Specification

 Description

HART Devices per Channel

Max 8 (total of 64 HART devices per PLX51-HART-8I module)

Configurable Update Rate

Supported

Configurable HART Requests

Supported

Burst Mode

Supported

Pass-through Requests

Supported

Device Type Manager (DTM)

Available

Analog Input Channel

 

Specification

 Description

Number of Channels

8

ADC Resolution

12-bit

Input Impedance

 250 Ω

Accuracy (calibrated 25°C)

 < 0.15 %

Accuracy (uncalibrated)

 < 0.30 %

Current Range

 0–22mA

Current Limit

 34mA

Voltage Range

0–10Vdc

Voltage Limit

11Vdc

Isolated

Yes

Input Filter

Supported

Input Types Supported

Voltage
Current 0-20mA
Current 4-20mA
Current 0-20mA (with external Resistor)
Current 4-20mA (with external Resistor)

Analog Scaling

Supported

Ethernet

 

Specification

 Description

Connector

RJ45

Conductors

CAT5 STP/UTP

ARP Connections

Max 200

TCP Connections

Max 200

CIP Connections

Max 20

Communication Rate

10/100 Mbps

Duplex Mode

Full / Half

Auto MDIX support

Yes

Embedded Switch

Yes, 2x Ethernet Ports

Device Level Ring (DLR)

Supported

Network Time Protocol (NTP)

Supported

1588 Precision Time Protocol (PTP)

Supported

 

EtherNet/IP

 

Specification

 Description

EtherNet/IP Target

Class 1 Cyclic Connection Count

8

EtherNet/IP Originator

Class 1 Cyclic Connections Supported

Yes

Class 3 / UCMM Connections Supported

Yes

Class 1 Connection Count

10

Class 3 / UCMM Target Device Count

10

Class 3 / UCMM Mapping Count

50

 

 Modbus

 

Specification

 Description

Client

Modes Supported

 Modbus TCP, Modbus RTU232, Modbus, RTU485

Modbus RTU485 Termination

125 Ω - Software Enabled

Max. Modbus Server Devices

20

Max. Modbus Mapping

100

Mapping Ranges

Holding Register 0 to 65535
Input Register 0 to 65535
Input Status 0 to 65535
Coil Status 0 to 65535

Base Offset

Modbus (Base 0)
PLC (Base 1)

Configurable Modbus TCP Port

Yes

Data Reformatting Supported

BB AA
BB AA DD CC
CC DD AA BB
DD CC BB AA

Server

Modes Supported

Modbus TCP, Modbus RTU232, Modbus, RTU485 (simultaneous)

Modbus RTU485 Termination

Software set

Mapping Ranges

 Holding Register 0 to 65535
Input Register 0 to 65535
Input Status 0 to 65535
Coil Status 0 to 65535

Base Offset

Modbus (Base 0)
PLC (Base 1)

Configurable Modbus TCP Port

Yes

 

Serial Port (RS232/RS485)

 

Specification

 Description

RS232

RS232 Connector

9-way terminal (shared with RS485)

RS232 Conductor

24 – 18 AWG

Electrical Isolation

 1000Vdc

Baud Rates

1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200

Parity

None, Even, Odd

Data bits

8

Stop bits

1

RS485

RS485 Connector

9-way terminal (shared with RS485)

RS485 Conductor

24 – 18 AWG

Electrical Isolation

1500 Vrms for 1 minute

Baud Rates

1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200

Parity

None, Even, Odd

Data bits

8

Stop bits

1

硬件

Electrical

Specification

 Description

Power requirements Input:

10 – 32Vdc, (121mA @ 24Vdc)

Voltage Fluctuations

Voltage fluctuations < ±10%
Transient Over-voltages up to the levels of
OVERVOLTAGE CATEGORY l

Power consumption

 3.1 W
300 mA maximum

Connector

3-way terminal

Conductors

 24 – 18 AWG

Earth connection

Yes, terminal based

Emissions

IEC61000-6-4

ESD Immunity

EN 61000-4-2

Radiated RF Immunity

IEC 61000-4-3

EFT/B Immunity

EFT: IEC 61000-4-4

Surge Immunity

Surge: IEC 61000-4-5

Conducted RF Immunity

IEC 61000-4-6

Note: The DC power supply or DC power source used by the PLX51-HART-8I must be classified as Limited Energy Circuits and Safety Extra Low Voltage (SELV).

 

Environmental

Specification

 Description

Enclosure Rating

IP20, NEMA/UL Open Type
Indoor use only

Temperature

-4°F to 149°F (-20°C to 65°C)

Relative Humidity

5% to 90% - No condensation

Pollution Degree

2

Altitude

< 2000 m

 

Hardware Specifications

 

Specification

 Description

Enclosure

Plastic

Dimensions (H x W x D)

101 x 22.5 x 120 mm (110 x 75.2 x 117.4)

Power Requirements

12 to 28Vdc (10 to 32Vdc)
121mA @ 24Vdc
35mA @ 24Vdc - With no field devices attached
130mA @ 24Vdc - With 4 field devices at 22mA each
64mA @ 12Vdc - With no field devices attached
160mA @ 12Vdc - With 4 field devices at 22mA each

Power Consumption

3.1 W
300 mA maximum
0.9 W - With no field devices attached
3.1 W - With 4 field devices at 22mA each
4.3 W - With input channels shorted
Power Connector 3-way terminal
Connector (Analog) 2-way terminal
Conductors 24 to 18 AWG

 

证书

UL Certificate of Compliance 366.73 kB 最后修改 2026.05.29
ODVA Declaration of Conformity 135.26 kB 最后修改 2026.05.29