The ProLinx EtherNet/IP to IEC60870-5-104 Client gateway creates a powerful connection between an EtherNet/IP network and IEC 104 server devices. The stand-alone, DIN-rail-mounted protocol gateway provides one Ethernet port.
The EtherNet/IP protocol supports the Explicit Messaging implementation of the protocol (PCCC-type messages). User-configurable as both a Client and a server, the EtherNet/IP port is a very powerful data transfer tool.
The IEC60870-5-104 Client protocol implementation allows the transfer of monitor and control data to and from remote servers.
Powerful network integration |
|
EtherNet/IP Client and Server |
|
IEC 60870-5-104 Client |
|
The ProLinx family EtherNet/IP to IEC 60870-5-104 Client communications module creates a powerful connection between an EtherNet/IP network and IEC 104 server devices. The module is a stand-alone DIN-rail mounted protocol gateway that provides one Ethernet port.
The EtherNet/IP™ protocol is one of the primary connectivity tools used by different
Rockwell Automation® platforms.
The Explicit Messaging aspect of the protocol has been implemented to provide asynchronous data transfer between the ProLinx gateway and Rockwell Automation hardware. |
|
Supported PLC Types |
PLC-2®, PLC-3®, PLC-5®, SLC™500, ControlLogix®, CompactLogix™, and MicroLogix™
|
Messaging Types |
As a Client, PCCC Explicit Messaging As a Server, PCCC or CIP Explicit Messaging |
Command Sets |
PLC-2/PLC-3/PLC5 Basic Command Set PLC5 Binary Command Set PLC5 ASCII Command Set SLC500 Command Set |
In server mode, the gateway accepts commands from one or more Clients to read/write data stored in the gateway’s internal registers.
Number of Connections |
5 |
Supported PLC Types |
PLC2, PLC5, SLC and ControlLogix file types supported |
Internal Database |
Data Table File Size: 100 or 1000 words Data Table File Start: N10 to N109 (based on file size set to 100) or N10 to N19 (based on file set to 1000) |
CIP Services Supported |
0x4C - CIP Data Table Read 0x4D - CIP Data Table Write |
In Client mode, the gateway controls the read/write data transfer between the gateway and other EtherNet/IP devices.
Number of Clients Supported |
1 |
Command List |
Support for 100 commands per Client, each configurable for command type, IP address, register to/from addressing and word/bit count. |
Polling of Command List |
User-configurable polling of commands, including disabled, continuous and on change of data (write only). |
Other Configurable Parameters |
Number of Commands (up to 100 per Client) Min Command Delay Response Timeout Retry Count Command Error Pointer |
Supported Message Types |
Accepts Client Monitor and Control Messages Supports all Edition 2 Causes of Transmission |
|
Supported Data Types |
Monitor Points: M_SP_NA M_DP_NA M_ST_NA M_BO_NA M_ME_NA, NB, NC M_IT_NA |
Control Points: C_SC_NA C_DC_NA C_BO_NA C_RC_NA C_SE_NA, NB, NC
|
Maximum number of points (per Data Type)
|
1000 Points for all Supported Data Types, except 4000 total data words, maximum |
|
Maximum number of commands |
500 commands maximum for all four clients |
|
Event Message Support |
Timestamp events are transferred to the other protocol through the mailbox feature. |
|
Configurable Parameters |
t1 timeout set value t2 timeout set value t3 timeout set value k (maximum queue) w (latest ack threshold) |
The ProLinx module contains an internal database that consists of areas for application data, status information, and configuration information.
The internal database is shared between all ports on the module and is used as a conduit to pass information from a device on one network to one or more devices on another network.
The data area is used to store and retrieve data by the protocol drivers and for data exchange between protocols. The database is used as a source for write commands to remote devices and holds data collected from the remote devices. Commands defined in the configuration file (stored in the configuration data area) control how the data is to be handled in the database.
This area is used to store error codes, counters, and port status information for each port.
This area contains module configuration information such as port configuration, network information, and command configuration. This configuration file is downloaded to, or uploaded from, this area.
Specification |
Description |
Power Supply |
24 VDC nominal |
Current Load |
500 mA max @ 32 VDC max |
Operating Temperature |
-4° F to 122° F (-20° C to 50° C) |
Storage Temperature |
-40° F to 185° F (-40° C to 85° C) |
Relative Humidity |
5% to 95% (with no condensation ) |
Dimensions |
Standard: |
LED Indicators |
Power and Module Status |
Configuration Serial Port |
DB-9M RS-232 only |
Ethernet Port (Ethernet modules only) |
10Base-T half duplex RJ45 Connector |
Application Ports |
Modbus Plus Connector |
Serial Port Isolation |
2500 V RMS port signal isolation per UL 1577 |
Shipped with Each Unit |
Mini-DIN to DB-9M serial cables |
DFNT-104C Datasheet | 232.49 kB | 最后修改 2013.06.25 |
DFNT Protocol Manual | 2.03 MB | 最后修改 2013.07.24 |
ProSoft Configuration Builder (PCB) | ||
LifeCycle Letter 5000 Selected Series | 114.23 kB | 最后修改 2023.11.13 |
104C Protocol Manual | 1.80 MB | 最后修改 2014.05.23 |
ProLinx Reference Guide | 1.52 MB | 最后修改 2014.11.12 |
CB Safety | 35.78 kB | 最后修改 2022.04.27 |
Korean KC Registration | 807.00 kB | 最后修改 2020.03.13 |
Country Approval - Eurasian Customs Union Conformity (EAC) (Wired) | 1.92 MB | 最后修改 2020.07.10 |
UL/cUL; Class 1, Div 2 | 1.08 MB | 最后修改 2020.03.31 |
UL Certificate of Compliance - Canada | 1.10 MB | 最后修改 2022.11.16 |