Why am I unable to download my Config file to my PTQ module?

The setup jumper must be off or unpinned in order for the module to accept a config file....

Read more

Do you have samples for your PTQ modules in ProWorx or ModSoft format? I see information for Concept and Unity, but nothing for ProWorx or any other programming environment.

Per the recommendation of Schneider, we do not provide any samples for programming packages besides Concept and Unity. This does not mean that the module will not work in this environment; it just means there are no samples for this. Since the PTQ module is responsible for sendin...

Read more

What is the purpose of the battery on the PTQ modules?

The battery is a lithium rechargeable type.The battery is used for the RTC (real-time clock) and CMOS RAM. Unless the customer changes the CMOS settings and afterwards the battery were to die, (after about 3 weeks) the CMOS settings would be lost and revert to the default CMOS s...

Read more

Can my PTQ module be configured with Unity Pro software?

All ProSoft PTQ modules are configured with the ProSoft Configuration Builder software that is provided with the module. PTQ modules will work with Modicon Quantum processors that have been programmed with ModSoft, ProWorxNxT, ProWorx 32, Concept, Unity Pro or other Quantum progr...

Read more

How many PTQ modules can be added to a Quantum Rack?

Each specific model of Quantum processor has a limit on how many Option modules are supported by that processor. PTQ modules are considered Option Modules, as are other communications modules, like RIO HEAD, NOM, NOE, and NOX Option modules. To determine how many PTQ modules may ...

Read more

The order of bits in the Binary Inputs and Outputs of my PTQ-DNP module appear to be the opposite of what I expect. Why?

When transferring Binary Inputs and Outputs to or from a Modicon Quantum CPU using the PTQ-DNP module, the bit pattern appears to be reversed, most-significant to least significant and vise versa.  In other words, to set DNP BI point 0, you have to set bit 15 in the 4X Holdi...

Read more