MVI69 modules require 800ma @ 5 volts and have a Distance Rating of 2 (slots from a power supply) MVI69E modules require 500ma @5 volts and have a Distance Rating of 4 MVI69L modules require 450ma
Read moreAt this time, our InRAx line of DNP3 serial communications solutions offer 2 DNP serial ports. One will always be available as a DNP slave to provide data to a DNP serial master system. The other
Read morephysical media so that they are able to monitor the network for the presence of a Scanner. 2) The AN-X-Mod gateways have built-in termination so they need to be connected to the Modicon splitter ... Can I use 2 AN-X-MOD gateways running as scanners in a redundant application?
Read moreThe MVI56E-MCM and MVI56E-MCMR modules share nearly the same Modbus functionality, but the MVI56E-MCMR module pages user data in a block of 40 words at a time as opposed to 200 words for the MCM
Read more# is the offset from the start of the analog # input database. # # point# class deadband start 6 1 50 7 1 10 8 2 100 end The AI Deadband being set to a value of 1000
Read more