What is the difference between the 3150-MCM and the MVI46-MCM

The MVI46-MCM: Is the latest Modbus module for the Allen-Bradley ;SLC platform Provides a debug port which allows the user to view module configuration and status Provides a built-in data analyzer for troubleshooting communication problems with the attached Modbus devices Is...

Read more

What is the Mean Time Between Failure (MTBF) for the 3150-MCM and 3100-MCM?

The MTBF for the 3150/3100 module line is 8,602,880 hours....

Read more

Is the DH-485 port on the 3150 module available for use?

No, the ProSoft 3150 product line is based on the Allen-Bradley KE module, which supports DH-485. On the 3150 products, the DH-485 port is disabled. The two serial DB9 ports are available to the user....

Read more

Which of your products support RS-485 serial protocols?

Almost all ProSoft solutions for serial based protocols support RS-232C, RS-485 and RS-422 electrical interface types, but equally important is the 'language' or application layer protocol needed for your application.ProSoft solutions are categorizedby the required protocols, not...

Read more

My 3150-MCM is configured to have no Write Data, only Read Data. Occasionally, I am seeing my data overwritten with what appears to be configuration data.

3150-MCM write block count and write block start are both set to 0. The write block start parameter must be set to a value which does not overlap with the read data area. A write start value of 75 will generally take care of this problem. In the sample ladder for the 3150-MCM, re...

Read more

When using the sample ladder I get an M0/M1 file reference error in my SLC processor if the MVI46 or 3150 is not in Slot 1.

The M0 and M1 files are slot referenced. The second digit in the address represents the slot number. If the MVI46 or 3150 module is in slot 1 (next to the processor), then the file reference is M0:1.XXXX and M1:1.XXXX If the module is in slot 5, then the file reference would b...

Read more

How do I deal with an unsigned integer in an SLC, PLC5, or MicroLogix processor?

Scenario: A device that uses an INT value to represent a range of 0 to 65535, but in the processor the INT tag has a range of -32768 to 32767.Since the A/B processor does not have an unsigned Integer data type, you will need to convert this value to represent the full range. Simp...

Read more

My 3150-MCM block IDs are incrementing until I connect the communications cable. Once the cable is connected, the block ID stops incrementing.

Verify the cable matches the diagram on page 50 of the user manual. If pins 7 and 8 are not jumpered, and there is communications on pins 1 or 9, your backplane transfers will fail. The error status data will also show an error code of 255....

Read more

What is the Mean Time Between Failure (MTBF) for the 3150-MCM and 3100-MCM?

The mtbf for the 3170 module line is 7,697,440 hours .. ...

Read more

What is the difference between 3150-MCM and 3150-DFM?

The 3150-MCM speaks Modbus communication. The 3150-DFM speaks DF1 communication.Related Keywords:3150-MCM 3150-DFM...

Read more